nVent.com
|
35
Raychem-AR-H
58686
-NGC
40
DemoUnit-EN-
1805
Step
4
–
NGC-
40
-HTC
3
General Setup
Setup the NGC-
40
-HTC
3
setpoint and alarm conditions as shown on the screen in
Step
3
.
The Local RTD will be your controlling sensor.
Step
5
–
NGC-
40
-SLIM General / Control
Click on the
Safety Limiter Temperature
button. The screen below will appear.
Click on the
Safety Temperature Limiter CAN ID
down arrow. The list will show all the NGC-
40
-SLIM modules connected on the CANbus.
In this demo there is only one NGC-
40
-SLIM module.
Select the NGC-
40
-SLIM module from the list. This is the module that is hardwired in the NGC-
40
Demo to be use with the NGC-
40
-SLIM.
The screen below will appear.
Set the
Limiter Trip Setpoint
to
310
°C