This demo will configure NGC-
40
-SLIM with the NGC-
40
-HTC
3
. The NGC-
40
DEMO has been pre-wired to the relay output of
the NGC-40
-HTC
3
module.
7.2 Configuring the NGC-40-SLIM module
IMPORTANT:
The NGC-
40
-HTC
3
module must be configured before beginning the testing of the NGC-
40
-SLIM. This includes the
temperature setpoint, High and Low temperature alarms.
TS
1
of the NGC-
40
-SLIM is configured at the HTC/HTC
3
module. TS
2
and TS
3
must be enabled at the NGC-
40
-SLIM screen. If a NGC-
40
-SLIM is detected on the CANbus then a setup button
(Safety Temperature Limiter)
will appear on the left hand side of the screen as
shown below. For DEMO purposes the NGC-
40
-HTC
3
will be used with the NGC-
40
-SLIM. The NGC-
40
-HTC
3
relay output and the NGC-
40
-SLIM relay output is physically tied within the demo.
Use to enter new temperature setpoint
Use to reset a tripped condition after the fault is cleared
Use to reset the alarm relay output after the fault condition is
cleared