Step
5
–
Creating a Digital Input Alarm
• Toggle the Digital Input switch on the NGC-
40
demo panel to the OPEN position. The Input LED on the NGC-
40
-IO module will change
from green to red and the Alarm LED turn ON (red).
Step
6
–
Viewing the Alarm List
Click on the Alarm List tab to review the alarms. The following screen should appear.
Step
6
–
Resetting the Alarms using the Reset buttons
• Click anywhere on the alarm message. The below screen will appear showing the reset options.
• Click on the Reset All button to clear both alarms.
IMPORTANT:
The alarms are still active therefore they will reappear on the alarm list until the faults are within alarm parameters.
Step
7
–
Resetting the alarms after faults cleared
• Wait until the alarms reappear.
• Turn TS
1
switch on the demo back to
79
°C.
• Toggle the Digital Input switch back to the Close position.
IMPORTANT:
The alarms clear automatically since they are not programmed as latching alarm.