Data Reporting Structure
62
UDACT Instruction Manual PN 50050:H 09/16/2002
By using the Type Mode feature, identification of zone/point types is possible. Limits for the maximum
number of zones/points reported for each panel are as follows:
AFP-100 = 198 points or 56 zones
AFP-200 = 99 zones
AFP-300 = 256 points or 99 zones
AFP-400 = 448 points or 99 zones
AFC-600 = 568 points or 99 zones
NFS-640 = 568 points or 99 zones
System 500 = 56 zones
System 5000 = 120 zones
System 5000 with AIM-200 = 248 zones
AM2020/AFP1010/INA = 568 points
NFS-3030 = 568 points or 568 zones
NCA = 568 point or 99 zones
Table 15 Type Mode Reporting Codes
Type
ID #
Activated Device
Report
2
Supervisory Alarm
E200 00 C001
3
Pull Station Alarm
E115 00 C003
4
Heat Sensor Alarm
E114 00 C004
5
Waterflow Alarm
E113 00 C005
6
Duct Detector Alarm
E116 00 C006
7
Flame Sensor Alarm
E117 00 C007
8
Smoke Zone Alarm
(Conventional)
E111 00 C002
9
Burglary
E130 00 C008
A
24 Hour Non-burglary
E150 00C009
B
High Temperature
E158 00 C010
C
Low Temperature
E159 00 C011
D
Low Water Pressure
E201 00 C012
E
Low Water Level
E204 00 C013
F
Pump Failure
E206 00 C014
Technical Manuals Online! - http://www.tech-man.com
Содержание UDACT
Страница 4: ...4 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 17: ...UDACT Instruction Manual PN 50050 H 09 16 2002 17 Notes Technical Manuals Online http www tech man com...
Страница 114: ...Point Assignments 114 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 120: ...Point Assignments 120 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 130: ...130 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...