UL Power-limited Wiring Requirements
UDACT Instruction Manual PN 50050:H 09/16/2002
27
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" away from any nonpower-limited circuit wiring.
Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must enter and exit
the cabinet through different knockouts and/or conduits.
Figure 10 Typical Wiring for UL Power-limited Requirements
Use power-limited source
Power-limited circuits
UDA
CT
-0
6.cd
r
Telephone Connections
Nonpower-limited circuits
Technical Manuals Online! - http://www.tech-man.com