Programming Options
34
UDACT Instruction Manual PN 50050:H 09/16/2002
UDACT Communication Selection (56)
Leaving address 56 at '0' disables communications to the Central Station(s). Enter '1' for zone reporting,
receive only, '2' for zone reporting, receive/transmit, '3' for point reporting, receive only, or '4' for point
reporting, receive/transmit. See "Type Mode" on page 55 for additional information on detailed
reporting.
Note:
Use receive only selection when using remote annunciators. Be certain to set one of the annunciators for
receive/transmit for EIA-485 communications bus supervision. Use the receive/transmit entry when annunciators are
not installed or when the UDACT receive/transmit function is to be used to supervise the EIA-485 communication bus.
For more information on the receive/transmit function, refer to annunciator manuals.
Backup Reporting (57)
Leaving address 57 at '0' means that reports will be transmitted to the secondary phone number only if
attempts to communicate to the primary phone number are unsuccessful. Programming a '1' causes all
reports to be transmitted to the secondary phone number.
Touchtone/Rotary Select (58)
A '0' programmed in this address by the factory triggers touchtone dialing over both telephone lines.
Select '1' for rotary dialing.
Make Break Ratio (59)
Use this address only if you have chosen '1' for address 58. The make/break ratio is factory set to '0'
which is 67/33, but may be changed to '1' which is a 62/38 ratio.
Address (60)
Leave default of 0.
Address (61)
Leave default of 0.
AC Loss Reporting Delay (62)
'0' is factory default which causes immediate reporting of AC loss. Valid entries are 0 to 9 and A to F
corresponding to the following reporting delay times: '1' = 6 hour, '2' = 7 hours, '3' = 8 hours, '4' = 9
hours, '5' = 10 hours, '6' = 11 hours, '7' = 15 hours, '8' = 16 hours, '9' = 17 hours, 'A' = 18 hours, 'B' = 19
hours, 'C' = 20 hours, 'D' = 21 hours, 'E' = 22 hours and 'F' = 23 hours.
Host Panel ID (63)
Enter one of the following digits corresponding to the Control Panel in which the UDACT is installed
.
A correct entry is essential for proper operation.
0 = AFP-100
3 = System 5000
6 = AFP-200 (Factory Default Setting)
1 = System 500
4 = System 5000 with AIM-200
7 = AM2020/AFP1010/INA, NCA, NFS-3030
2 = Do not use
5 = AFC-600, NFS-640
8 = AFP-300/AFP-400
9 = Do not use
Technical Manuals Online! - http://www.tech-man.com
Содержание UDACT
Страница 4: ...4 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 17: ...UDACT Instruction Manual PN 50050 H 09 16 2002 17 Notes Technical Manuals Online http www tech man com...
Страница 114: ...Point Assignments 114 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 120: ...Point Assignments 120 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 130: ...130 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...