Data Reporting Structure
UDACT Instruction Manual PN 50050:H 09/16/2002
61
Ademco Contact ID
The reporting structure for the Ademco Contact ID format is as follows:
SSSS 18 QXYZ GG CCC
Table 14 Ademco Contact ID Reporting Structure
Note:
For general reports (alarm, trouble and supervisory), the GG and CCC fields are transmitted as 00 and 000
unless changes to addresses 64-65 and 66-68 are made.
64 - 65 = Loop number (GG), (factory default is 00)
66 - 68 = Device/Zone number (CCC) for General Alarm, Fault or Supervisory messages (factory default is 000).
A typical printout of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows:
Note:
In the sample report, SD46 refers to smoke detector at address 46 or on zone 46.
Note:
18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the
alarm and trouble report.
Note:
Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or R
for New Restore.
Note:
CCCC, the first C is not transmitted by the UDACT but is printed by the Central Station Receiver printer output.
Continued on the next page...
SSSS
= Four digit Subscriber ID (addresses 17 - 20 and 43 - 46)
18
=
Identifies transmission as Contact ID to the receiver
at the Central Station
Q
= Event Qualifier; 1 = New Event, 2 = New Restore
XYZ
= Event Code (shown in Table 4 to Table 9)
GG
= Group or Loop number
CCC
= Device or Zone number
Time
Date
Rcvr/
Line ID
SSSS
QXYX
GG
CCCC
11:28
10/14
11
7777
E110
00
C000
General Alarm
11:28
10/14
11
7777
E111
00
C046
Alarm SD46
11:28
10/14
11
7777
E300
00
C000
General Trouble
11:28
10/14
11
7777
E380
00
C046
Trouble SD46
11:28
10/14
11
7777
R110
00
C000
General Alarm Restore
11:28
10/14
11
7777
R111
00
C046
Alarm SD46 Restore
11:28
10/14
11
7777
R300
00
C000
General Trouble Restore
11:28
10/14
11
7777
R380
00
C046
Trouble SD46 Restore
Technical Manuals Online! - http://www.tech-man.com
Содержание UDACT
Страница 4: ...4 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 17: ...UDACT Instruction Manual PN 50050 H 09 16 2002 17 Notes Technical Manuals Online http www tech man com...
Страница 114: ...Point Assignments 114 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 120: ...Point Assignments 120 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 130: ...130 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...