Ademco Contact ID Format
UDACT Instruction Manual PN 50050:H 09/16/2002
41
Ademco Contact ID Format
Primary Number
If 'E' is entered for address 16, the following data is automatically programmed for the primary phone number event
codes.
Enter a '000' for the data setting to disable the report.
Table 8 Ademco Contact ID, Primary Number
Notes:
1) Zero entries prevent the transmission of the report to the Central Station.
2) Refer to Contact ID program locations 64 - 68.
3) The identification of the zone/device number is automatically transmitted by the UDACT and is added to the main
event code. See Table 5-3 for more information.
4) For control panels; System 500, System 5000, AFP-200, AFP-400, AFC-600, NFS-640, AFP1010, AM2020, INA,
NFS-3030, and NCA the factory default event code is 110 and reprogrammable. The AFP-400 and AFP-100 are
unique in point reporting mode in that only the control module report codes are programmable. The factory setting of
report code 111 is fixed for addressable smoke detectors and cannot be changed.
5) AFP-200 applications transmit by zone, not by point.
6) The Group # is automatically incremented for AM2020/AFP1010/INA, NFS-3030 and NCA applications.
Address
Description
Setting
1
Group #
6
Sensor #
69-71
Primary# General Alarm Code
110
00
000
2
72-74
Primary # Zone/Point Alarm Code
5
110
4
00
Note
3
75-77
Primary # General Supervisory Code
200
00
000
2
78-80
Primary # Zone/Point Supervisory Code
5
200
00
Note
3
81-83
Primary # General Fault Code
300
00
84-86
Primary # AC Fault Code
301
00
87-89
Primary # Zone/Point Fault Code
5
380
00
Note
3
90-92
Primary # Low Battery Fault Code
302
00
93-95
Primary # Telco Primary Line Fault Code
351
00
96-98
Primary # Telco Secondary Line Fault Code
352
00
99-101
Primary # NAC Fault Code
321
00
102-104
Primary # Comm. Trouble Primary # Code
354
00
105-107
Primary # Comm. Trouble Secondary # Code
354
00
108-110
Primary # 485 Comm. Trouble Code
300
00
111-113
Primary # System Off Normal Code
308
00
114-116
Primary # UDACT Off Normal Code
350
00
117-119
Primary # System 24 Hour Test
602
00
120-122
Primary # System 24 Hour Test w/active event
608
00
123-125
Primary # Manual Test Message
601
00
Technical Manuals Online! - http://www.tech-man.com
Содержание UDACT
Страница 4: ...4 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 17: ...UDACT Instruction Manual PN 50050 H 09 16 2002 17 Notes Technical Manuals Online http www tech man com...
Страница 114: ...Point Assignments 114 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 120: ...Point Assignments 120 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 130: ...130 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...