Type Mode
UDACT Instruction Manual PN 50050:H 09/16/2002
55
Type Mode
CAUTION:
The UDACT fire protection and reporting capabilities are inactive while in Type Mode.
Type Mode may be used to disable reports by zone or point and to identify the specific functionality of
each zone or point in the system via Ademco Contact ID format. Factory default for all zones is Fire
Alarm. Use Type Mode to identify the function of each zone or point as follows:
Note:
On the AFP-100 when reporting point information, the factory default for addressable monitor modules is Fire
Alarm code 110 and the default for addressable detectors is Smoke Detector code 111. The smoke detector default
cannot be modified.
Note:
AM2020/AFP1010, INA, AFC-600, NFS-640, NFS-3030, and NCA applications restrict Type Mode
programming to a maximum of 568 points. All remaining points above 568 will report as fire alarm points.
☛
To access Type Mode press
MODE
, then
8973
, then
ENTER
/
STORE
.
8973
spells TYPE on a Touch-Tone® phone.
The UDACT will display three digits. For example, initial entry will display
01 0
.
The characters to the left identify the zone or point number. In this example, 01 identifies zone 01 or
point address 01. The character to the right (0 in this example) identifies the type of zone or point as
follows:
0 = Zone or point defined as fire alarm
1 = Disable zone or point report
2 = Zone or point defined as supervisory
3 = Zone or point defined as pull station
4 = Zone or point defined as heat detector
5 = Zone or point defined as waterflow
6 = Zone or point defined as duct detector
7 = Zone or point defined as flame sensor
8 = Zone or point defined as smoke zone (Use for group of addressable or conventional smoke
detectors and for addressable monitor modules monitoring conventional smoke detectors.)
9 = Zone or point defined as burglary
A = Zone or point defined as 24 hour non-burglary
B = Zone or point defined as high temperature
C = Zone or point defined as low temperature
D = Zone or point defined as low water pressure
E = Zone or point defined as low water level
F = Zone or point defined as pump failure
Factory default is all zones or points set to '0' for fire alarm. The '0' setting for zone reporting allows the
mixing of types of devices on a single zone. To change the type definition of the zone or point from the
factory default of 0, select 2 to F corresponding to the type of device(s) used (do not mix device types
for these settings), or select 1 to disable alarm reporting of any zone or point. The digit entered will
appear on the far right display. Next press the
ENTER
/
STORE
key. This stores the entry into E2 memory
and increments to the next higher address.
Continued on the next page...
General fire alarm
Burglary
Supervisory
24 hour non-burglary
Pull stations
High temperature
Heat detectors
Low temperature
Waterflows
Low water pressure
Duct detectors
Low water level
Flame sensor
Pump failure
Smoke zone
!
Technical Manuals Online! - http://www.tech-man.com
Содержание UDACT
Страница 4: ...4 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 17: ...UDACT Instruction Manual PN 50050 H 09 16 2002 17 Notes Technical Manuals Online http www tech man com...
Страница 114: ...Point Assignments 114 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 120: ...Point Assignments 120 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 130: ...130 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...