Programming Reference Sheets
44
UDACT Instruction Manual PN 50050:H 09/16/2002
59
Make/Break Ratio:
If rotary dialing is selected in Address 58; Enter '0' for a 67/73 make/
break ratio; '1' for a 62/38 make/break ratio.
60
Leave default of 0.
61
Leave default of 0.
62
AC Loss Reporting Delay:
Enter '0' for no time delay after AC loss; '1' for 6 hour delay; '2' for
7 hour delay; '3' for 8 hour delay; '4' for 9 hour delay; '5' for 10 hour delay; '6' for 11 hour delay; '7' for
15 hour delay; '8' for 16 hour delay; '9' for 17 hour delay; 'A' for 18 hour delay; 'B' for 19 hour delay; 'C'
for 20 hour delay; 'D' for 21 hour delay; 'E' for 22 hour delay; or 'F' for 23 hour delay.
63
Host Panel ID:
Enter '0' for AFP-100; '1' for System 500; '3' for System 5000; '4' for System
5000 with AIM-200; '5' for AFC-600, NFS-640; '7' for AM2020/AFP1010/INA, NCA, and NFS-3030;
'8' for AFP-300/AFP-400; or leave default of '6' for AFP-200; all other entries are invalid.
64
65
Loop Number:
Factory set to '00'. Valid entries are 00 through 97
66
67
68
Device/Zone Number for General Reports:
Factory set to '000'. Valid entries
are 000 through 999.
Technical Manuals Online! - http://www.tech-man.com
Содержание UDACT
Страница 4: ...4 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 17: ...UDACT Instruction Manual PN 50050 H 09 16 2002 17 Notes Technical Manuals Online http www tech man com...
Страница 114: ...Point Assignments 114 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 120: ...Point Assignments 120 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...
Страница 130: ...130 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...