background image

General

UDACT Instruction Manual  PN 50050:H  09/16/2002

121

Appendix K: INA

General

The UDACT is capable of reporting up to 2,040 points when used with the Intelligent Network 
Annunciator (INA). The first 568 points can be programmed using the Type Mode feature (refer to 
"Type Mode" on page 55). All points greater than 568 can be transmitted only as fire alarm points. For 
the UDACT to report a supervisory point to the central station, both the FACP and the UDACT must 
have the point programmed as supervisory. Failure to program the panel or UDACT correctly will result 
in a fire alarm signal being transmitted to the central station.

Note: 

The UDACT does not support voice and burglary options when used with the INA. Refer to the 

Intelligent 

Network Annunciator Manual

 for additional restrictions and more information.

Mounting

The UDACT may be mounted in the INA control panel enclosure or be mounted remotely using an 
ABS-8R 

or UBS-1 enclosure placed within 6000 feet (1828.8 meters) of the control panel.

For mounting instructions see "Remote Installation" on page 22 or 

"Internal Installation" on page 20

.

Wiring

CAUTION: 

Remove all power from the control panel by disconnecting AC and batteries

 before 

making any connections to prevent personal and/or circuit damage.

Connections

Refer to Figure 33 and Figure 34 on page 122. 

Connect the communication line between the EIA-485 terminal block on the INA and TB-1 terminals 3 
and 4 on the UDACT, being certain to observe polarity.

If no other devices are connected to the EIA-485, install a 120 ohm EOL resistor across UDACT 
TB1 terminals 3 and 4.

Connect the 

Ground Wire (PN 71073, provided)

 from the UDACT 

EARTH

 terminal on TB3 to the CHS-4 

Chassis or to a solid building earth ground.

Connect 24 VDC filtered, regulated power from the MPS-24A or MPS-24B (Main Power Supply) to 
TB1 terminals 1 and 2 on the UDACT.

Notes:

1. Ferrite cores, PN 29090, are recommended for all applications.

2. Recommended wire is 12 AWG (3.25mm

2

) to 18 AWG (0.75mm

2

), twisted pair, shielded cable.   

Connect only one end of shield: a) shield may be connected to cabinet (earth ground) at fire alarm 
panel, or b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT as shown in Figure 33

Note: 

The shield end that is not connected should be insulated to prevent accidental grounding. Do not connect both 

ends of shield under any circumstance since a ground fault may result.

3. Conduit is recommended for external wire runs. Consult local building codes.

4. Refer to "Specifications" on page 13 for power requirements.

!

Technical Manuals Online! - http://www.tech-man.com

Содержание UDACT

Страница 1: ...Universal Digital Alarm Communicator Transmitter UDACT Instruction Manual H PN 50050 H ECN 02 266 Document 50050 09 16 2002 Rev Technical Manuals Online http www tech man com...

Страница 2: ...ning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detecto...

Страница 3: ...ing filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former a...

Страница 4: ...4 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...

Страница 5: ...ecial Functions 15 Normal Mode 15 Program Mode 15 Type Mode 15 Troubleshoot Mode 15 Lamp Test Mode 15 Clear Function 16 Manual Test Function 16 Installation and Wiring Installation 19 Options 19 Power...

Страница 6: ...e Clock 36 End Programming 36 3 1 4 1 Express and 4 1 Standard Formats 37 Primary Number 37 Secondary Number 38 4 2 Standard and 4 2 Express Formats 39 Primary Number 39 Secondary Number 40 Ademco Con...

Страница 7: ...ot Position 79 Mounting 80 Wiring 80 Connections 80 Zone Assignments with AIM 200 82 Zone Assignments without AIM 200 83 Appendix E AFP 300 AFP 400 General 85 AFP 300 85 AFP 400 85 Mounting 85 Wiring...

Страница 8: ...Code Report Transmission 105 For Zone Reporting 105 For Point Reporting 105 Appendix H NCA General 107 Mounting 107 Wiring 107 Connections 107 Appendix I AM2020 AFP1010 General 109 Mounting 109 Wiring...

Страница 9: ...llation Manual 15583 AFP 100 AFP 100 Instruction Manual 51010 AFP 200 AFP 200 Instruction Manual 15511 AFP 300 AFP 400 AFP 300 AFP 400 Installation Manual 50253 AFC 600 AFC 600 Installation Manual 510...

Страница 10: ...on Manual master transmission clear function Mounts in separate ABS 8R or UBS 1 enclosure Communicates vital system status including Independent zone point alarm trouble and supervisory AC main power...

Страница 11: ...UDACT with the corresponding panel Table 1 Compatible FACP Firmware CLEAR TEST MODE Up Arrow Down Arrow Digits 0 9 1st EVENT ENTER STORE Letters A F UDACT 01 cdr COMM FAIL Yellow LED KISS OFF Green LE...

Страница 12: ...o wire EIA 485 serial interface which is power limited and supervised by the control panel and the UDACT The wiring connections are made to the RS RS and Shield terminals of TB1 on the UDACT The EIA 4...

Страница 13: ...nector Supervision Threshold less than 4 0 volts for 2 minutes The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive REN on the telephone line may...

Страница 14: ...operate to the user s satisfaction Before installing this equipment users should ensure that it is permissible to be connected to the facilities of the local telecommunications company The equipment m...

Страница 15: ...program mode it cannot receive host FACP status information Refer to Programming Instructions on page 29 for complete information Type Mode Type Mode is used to define the specific type of device poi...

Страница 16: ...auses the UDACT to immediately stop transmissions hang up from the telephone network and clear out any messages that were waiting for transmission and reset Manual Test Function The manual test functi...

Страница 17: ...UDACT Instruction Manual PN 50050 H 09 16 2002 17 Notes Technical Manuals Online http www tech man com...

Страница 18: ...Modes and Special Functions 18 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...

Страница 19: ...cific Fire Alarm Control Panel will be found in the appropriate appendix relating to that panel Table 2 Installation Options Fire Alarm Control Panel Cabinet Style Where Installed AFP 100 SBB 1 Intern...

Страница 20: ...CT as shown below 3 Install one aluminum nylon standoff and one aluminum standoff onto the studs of the chassis slot in which the UDACT is to be installed Tighten securely 4 Position the UDACT on the...

Страница 21: ...described and shown below Figure 3 CHS M2 Installation Step Action 1 Disconnect AC power and disconnect batteries 2 Insert the tab at the bottom of the board into the chassis slot as indicated 3 Posit...

Страница 22: ...sure is detailed below Figure 4 ABS 8R RB Installation Step Action 1 Align the UDACT to the four 4 threaded standoffs at the back of the ABS 8R RB or UBS 1 enclosure 2 Secure using the four 4 screws s...

Страница 23: ...Connection The EIA 485 Serial Interface is connected between the Fire Alarm Control Panel and the UDACT using twisted pair shielded cable Recommended wire size is 12 AWG 3 25mm2 to 18 AWG 0 75mm2 For...

Страница 24: ...DACT be located as the first device on the incoming telephone circuit to properly function Figure 7 Wiring Phone Jacks 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 UDACT 03 cdr RJ31X Jack RJ31X Jack Ring Tip Ring...

Страница 25: ...the UDACT is programmed for Receive Only typically this occurs when annunciators are also used and are set for Receive Transmit the relay output is used to provide a UDACT trouble input to the host c...

Страница 26: ...S LOOP 0 NO ON MR 101 C NC C 18 24 115 230 24 VDC Comm FAILURE EARTH TB3 SLC from FACP Continuation of SLC FMM 1 UDACT 47K EOL Resistor included UDACT 05 cdr Note FMM 1 Monitor Module is used to super...

Страница 27: ...must remain at least 0 25 away from any nonpower limited circuit wiring Furthermore all power limited circuit wiring and nonpower limited circuit wiring must enter and exit the cabinet through differe...

Страница 28: ...UL Power limited Wiring Requirements 28 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...

Страница 29: ...ou enter information into the UDACT the digits will scroll across the display from right to left You are allowed a pause of up to 10 seconds in between each number while entering the code After pressi...

Страница 30: ...ntries for both the primary and secondary phone numbers are 0 F with the numeric digits as dialed numbers and hexadecimal digits A F representing the following functions A on a Touchtone phone keypad...

Страница 31: ...This can be avoided by using the up or down arrows to navigate through programming locations Primary Number Account Code 17 20 Four locations at addresses 17 20 default to all 0 s Valid entries are 0...

Страница 32: ...active but do not identify the specific zone or point Choose one entry from the list below CAUTION Default entries for event codes are always programmed into memory when ENTER STORE is pressed at this...

Страница 33: ...reporting range of the UDACT Table 3 Start and End Monitoring Addresses Note For additional information on the starting and ending addresses refer to the host FACP Manual ZONE REPORTING START Factory...

Страница 34: ...ing a 1 causes all reports to be transmitted to the secondary phone number Touchtone Rotary Select 58 A 0 programmed in this address by the factory triggers touchtone dialing over both telephone lines...

Страница 35: ...panel Loop Number 00 reports points zones 00 001 to 00 999 Loop Number 01 reports points zones 01 000 to 01 999 Loop Number 02 reports points zones 02 000 to 02 040 If the Loop Number 64 65 is program...

Страница 36: ...his report is generated in place of the normal test report when an alarm and or trouble condition exists at the time the test report is due to be sent Programming the Real Time Clock Entering an addre...

Страница 37: ...ary Line Fault Code F 79 Primary NAC Fault Code F 80 Primary Comm Trouble Primary Code F 81 Primary Comm Trouble Secondary Code F 82 Primary 485 Comm Trouble Code F 83 Primary System Off Normal Code F...

Страница 38: ...C Fault Code F 150 Secondary Comm Trouble Primary Code F 151 Secondary Comm Trouble Secondary Code F 152 Secondary 485 Comm Trouble Code F 153 Secondary System Off Normal Code F 154 Secondary UDACT Of...

Страница 39: ...91 92 Primary Comm Trouble Primary Code FD 93 94 Primary Comm Trouble Secondary Code FE 95 96 Primary 485 Comm Trouble Code FE 97 98 Primary System Off Normal Code FF 99 100 Primary UDACT Off Normal...

Страница 40: ...m Trouble Primary Code FD 163 164 Secondary Comm Trouble Secondary Code FE 165 166 Secondary 485 Comm Trouble Code FE 167 168 Secondary System Off Normal Code FF 169 170 Secondary UDACT Off Normal Cod...

Страница 41: ...smoke detectors and cannot be changed 5 AFP 200 applications transmit by zone not by point 6 The Group is automatically incremented for AM2020 AFP1010 INA NFS 3030 and NCA applications Address Descri...

Страница 42: ...changed 5 AFP 200 applications transmit by zone not by point 6 The Group is automatically incremented for AM2020 AFP1010 INA applications Address Description Setting1 Group 6 Sensor 139 141 Secondary...

Страница 43: ...46 Secondary Account Code Valid keys are 0 F 47 48 49 50 Secondary 24 Hour Test Time Enter military time 1400 for 2 PM 51 Secondary Number Test Time Interval Enter 0 for 24 hour 1 12 hour 52 53 Start...

Страница 44: ...5 hour delay 8 for 16 hour delay 9 for 17 hour delay A for 18 hour delay B for 19 hour delay C for 20 hour delay D for 21 hour delay E for 22 hour delay or F for 23 hour delay 63 Host Panel ID Enter 0...

Страница 45: ...12 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 1...

Страница 46: ...1 32 33 34 35 36 37 38 39 40 41 F F F F F F F F F F F F F F F F Secondary Communication Format Secondary 24 Hour Test Time 42 E 47 48 49 50 0 0 0 0 Secondary Account Code Secondary Number Test Time In...

Страница 47: ...A A B E C E D 125 126 127 128 129 130 131 132 133 134 135 136 137 138 E E E E E F E F 9 9 9 1 9 2 139 140 141 142 143 144 145 146 147 148 149 150 151 152 1 1 0 0 8 1 0 0 F 1 F 6 0 0 153 154 155 156 1...

Страница 48: ...Factory Default Settings 48 UDACT Instruction Manual PN 50050 H 09 16 2002 Notes Technical Manuals Online http www tech man com...

Страница 49: ...he function keys in Normal Mode Figure 12 UDACT Keypad Clear The Clear function will cause the UDACT to cease transmissions clear any active or pending transmissions reset and return to normal system...

Страница 50: ...he Up Arrow and Down Arrow keys are used to display UDACT fault conditions Press the 1ST EVENT key at any time to display the first event that occurred Down Arrow Use the Down Arrow key to view other...

Страница 51: ...green LED that remains on while power is supplied to the UDACT If this indicator fails to light under normal conditions service the system immediately Kiss Off A green LED that blinks when the Centra...

Страница 52: ...lity provided for both the primary and secondary telephone line interfaces Any time that the UDACT needs to make a call to the Central Station line seizure will disconnect any local premises phones sh...

Страница 53: ...or the pulsed and Ademco Express formats These reports are factory programmed for active transmission when using the Ademco Contact ID Event Activations Event Restorals 1 General Alarm 19 General Alar...

Страница 54: ...UDACT will transmit a test report to both Central Stations at programmed intervals typically every 24 hours Should there exist an abnormal condition in the fire alarm system such as an alarm trouble...

Страница 55: ...nt defined as supervisory 3 Zone or point defined as pull station 4 Zone or point defined as heat detector 5 Zone or point defined as waterflow 6 Zone or point defined as duct detector 7 Zone or point...

Страница 56: ...points unless disabled in the Type Mode Disabling zones or points also prohibits the activation shorted or alarm activated condition from being reported by the UDACT Disabling of the zone or point doe...

Страница 57: ...essed the display will move the C or D character one position to the left while placing the digit to be dialed on the farthest right display position Continue to press the phone numbers to be dialed S...

Страница 58: ...Lamp Test Mode 58 UDACT Instruction Manual PN 50050 H 09 16 2002 Notes Technical Manuals Online http www tech man com...

Страница 59: ...pecific zone or point is desired Use Ademco Contact ID for specific zone or point identification Table 12 Data Reporting Structure Note Refer to Table 17 on page 65 for a list of compatible receivers...

Страница 60: ...rouble 2nd digit RTS System Trouble Restore 1st digit RTS2 System Trouble Restore 2nd digit L Low Battery 1st digit L2 Low Battery 2nd digit RL Low Battery Restore 1st digit RL2 Low Battery Restore 2n...

Страница 61: ...e report Note Q which is the Event Qualifier for the reporting structure is printed out in the report as an E for New Event or R for New Restore Note CCCC the first C is not transmitted by the UDACT b...

Страница 62: ...0 248 zones AM2020 AFP1010 INA 568 points NFS 3030 568 points or 568 zones NCA 568 point or 99 zones Table 15 Type Mode Reporting Codes Type ID Activated Device Report 2 Supervisory Alarm E200 00 C001...

Страница 63: ...Mode Maximum Address FACP Maximum Address System 500 56 AFP 100 198 AFP 200 99 System 5000 120 System 5000 with AIM 200 248 AFP 300 256 AFP 400 448 AFC 600 568 NFS 640 568 AM2020 AFP1010 INA 568 NCA...

Страница 64: ...Data Reporting Structure 64 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...

Страница 65: ...control card at Rev 1 4 software and Rev C line card at Rev 1 5 software 8 Model 2 only 9 Version 1 62 software Table 17 Compatible UL Listed Receivers Ademco 685 1 Silent Knight 9000 ITI CS 4000 3 FB...

Страница 66: ...UL Listed Receivers 66 UDACT Instruction Manual PN 50050 H 09 16 2002 Notes Technical Manuals Online http www tech man com...

Страница 67: ...isconnect all sources of power AC and DC 2 Install 3 nylon and 1 aluminum 5 8 long snap in standoffs provided in the holes located on the right side of the circuit board 3 Place the SW2 switch in the...

Страница 68: ...red non resettable power from terminal block TB4 on the AFP 100 to TB1 terminals 1 and 2 on the UDACT Notes 1 Ferrite cores PN 29090 are recommended for all applications 2 Recommended wire is 12 AWG 3...

Страница 69: ...Type Mode refer to Type Mode on page 55 to match the function of remaining zones in the system for proper reporting Table 19 Zone Assignments AFP 100 Zone Zone Function Zone Zone Function 1 29 2 30 3...

Страница 70: ...154 005 055 105 155 006 056 106 156 007 057 107 157 008 058 108 158 009 059 109 159 010 060 110 160 011 061 111 161 012 062 112 162 013 063 113 163 014 064 114 164 015 065 115 165 016 066 116 166 017...

Страница 71: ...rity If last device or no other devices are connected to the EIA 485 install a 120 ohm EOL resistor PN 71244 across UDACT TB1 terminals 3 and 4 Connect the Ground Wire PN 71073 provided from the UDACT...

Страница 72: ...ith an AFP 200 Figure 17 UDACT and AFP 200 EARTH Comm FAILURE 24V 24V GND RS RS SHIELD RS Rs ACS TERM TERM UDACT 09 cdr Solid Earth Ground Connection To Phone Lines supervised DO NOT USE AFP 200 Cabin...

Страница 73: ...glary zones modify the general supervisory report at addresses 75 77 and 145 147 to report general burglary Table 23 Zone Assignments AFP 200 Zone Zone Function Zone Zone Function Zone Zone Function 1...

Страница 74: ...Zone Assignments 74 UDACT Instruction Manual PN 50050 H 09 16 2002 Notes Technical Manuals Online http www tech man com...

Страница 75: ...line between the EIA 485 terminal block on the System 500 and TB 1 terminals 3 and 4 on the UDACT being certain to observe polarity If last devices or no other devices are connected to the EIA 485 ins...

Страница 76: ...ACT and System 500 EARTH Comm FAILURE 24V 24V GND RS RS SHIELD RS Rs ACS TERM TERM COMMON COMMON 24V POWER 24V RESET BATT BATT Solid Earth Ground Connection To Phone Lines supervised UDACT 10 cdr Syst...

Страница 77: ...ype Mode refer to Type Mode on page 55 to match the function of remaining zones in the system for proper reporting Table 25 Zone Assignments System 500 Zone Zone Function Zone Zone Function 1 29 2 30...

Страница 78: ...Zone Assignments 78 UDACT Instruction Manual PN 50050 H 09 16 2002 Notes Technical Manuals Online http www tech man com...

Страница 79: ...ble 26 Using AIM 200 Module Configured as 8 Zone Input Module AIM 200 modules placed into any module slot location must be configured as an 8 Zone Input module except the first module slot position Pr...

Страница 80: ...stor across UDACT TB1 terminals 3 and 4 Connect the Ground Wire PN 71073 provided from the UDACT EARTH terminal on TB3 to the CHS 4 Chassis or to a solid building earth ground Connect 24 VDC filtered...

Страница 81: ...Comm FAILURE 24V 24V GND RS RS SHIELD RS Rs ACS TERM TERM COMMON COMMON BATT 24V POWER 24V RESET BATT UDACT 12 cdr Solid Earth Ground Connection To Phone Lines supervised ABS 8R or UBS 1 System 5000 C...

Страница 82: ...or proper reporting Continued on the next page Zone Zone Function Zone Zone Function Zone Zone Function 1 42 83 2 43 84 3 44 85 4 45 86 5 46 87 6 47 88 7 48 89 8 49 90 9 50 91 10 51 92 11 52 93 12 53...

Страница 83: ...Function Zone Zone Function Zone Zone Function 124 166 208 125 167 209 126 168 210 127 169 211 128 170 212 129 171 213 130 172 214 131 173 215 132 174 216 133 175 217 134 176 218 135 177 219 136 178 2...

Страница 84: ...Zone Function 1 41 81 2 42 82 3 43 83 4 44 84 5 45 85 6 46 86 7 47 87 8 48 88 9 49 89 10 50 90 11 51 91 12 52 92 13 53 93 14 54 94 15 55 95 16 56 96 17 57 97 18 58 98 19 59 99 20 60 100 21 61 101 22...

Страница 85: ...line between the EIA 485 terminal block TB4 on the AFP 300 AFP 400 and TB1 terminals 3 and 4 on the UDACT being certain to observe polarity If no other devices are connected to the EIA 485 install a...

Страница 86: ...CT and AFP 300 AFP 400 in CAB 3 4 EARTH Comm FAILURE 24V 24V GND RS RS SHIELD RS Rs ACS TERM TERM To Phone Lines supervised Solid Earth Ground Connection ABS 8R or UBS 1 CAB 400AA Cabinet CPU 300 400...

Страница 87: ...Addresses 01 96 Loop 2 Modules 201 296 are programmed by Type Mode Entries Addresses 101 196 Loop 1 Detectors 101 196 are programmed by Type Mode Entries Addresses 201 296 Loop 2 Detectors 201 296 ar...

Страница 88: ...only CAUTION Point reports for Loop 1 Modules 197 through 199 Detectors 197 through 199 and point reports for Loop 2 Modules 297 through 299 and Detectors 297 through 299 are omitted However when dev...

Страница 89: ...g burglary zones modify the general supervisory report at addresses 75 77 and 145 147 to report general burglary Table 34 Zone Assignments AFP 300 AFP 400 Zone Zone Function Zone Zone Function Zone Zo...

Страница 90: ...54 005 055 105 155 006 056 106 156 007 057 107 157 008 058 108 158 009 059 109 159 010 060 110 160 011 061 111 161 012 062 112 162 013 063 113 163 014 064 114 164 015 065 115 165 016 066 116 166 017 0...

Страница 91: ...259 309 359 210 260 310 360 211 261 311 361 212 262 312 362 213 263 313 363 214 264 314 364 215 265 315 365 216 266 316 366 217 267 317 367 218 268 318 368 219 269 319 369 220 270 320 370 221 271 321...

Страница 92: ...ix C Table 38 Point Assignments AFP 300 AFP 400 Point No Type of Device System 5000 Output Modules Point No Type of Device System 5000 Output Modules 401 451 402 452 403 453 404 454 405 455 406 456 40...

Страница 93: ...1 terminals 3 and 4 on the UDACT being certain to observe polarity If no other devices are connected to the EIA 485 install a 120 ohm EOL resistor across UDACT TB1 terminals 3 and 4 Connect the Ground...

Страница 94: ...T and AFC 600 in CAB 3 4 EARTH Comm FAILURE 24V 24V GND RS RS SHIELD RS Rs ACS TERM TERM To Phone Lines supervised Solid Earth Ground Connection ABS 8R or UBS 1 CAB 600AA Cabinet CPU 600 MPS 6 UDACT 1...

Страница 95: ...Addresses 385 448 Loop 1 Detectors 65 128 are programmed by Type Mode Entries Addresses 449 512 Loop 2 Detectors 65 128 are programmed by Type Mode Entries Addresses 513 576 Event Code Report Transmis...

Страница 96: ...selecting burglary zones modify the general supervisory report at addresses 75 77 and 145 147 to report general burglary Table 40 Zone Assignments Zone Zone Function Zone Zone Function Zone Zone Funct...

Страница 97: ...p 1 Point No Type of Device Module Loop 2 Point No Type of Device Module Loop 2 001 033 065 097 002 034 066 098 003 035 067 099 004 036 068 100 005 037 069 101 006 038 070 102 007 039 071 103 008 040...

Страница 98: ...7 132 164 196 228 133 165 197 229 134 166 198 230 135 167 199 231 136 168 200 232 137 169 201 233 138 170 202 234 139 171 203 235 140 172 204 236 141 173 205 237 142 174 206 238 143 175 207 239 144 17...

Страница 99: ...257 289 321 353 258 290 322 354 259 291 323 355 260 292 324 356 261 293 325 357 262 294 326 358 263 295 327 359 264 296 328 360 265 297 329 361 266 298 330 362 267 299 331 363 268 300 332 364 269 301...

Страница 100: ...ctor Loop 1 385 417 449 481 386 418 450 482 387 419 451 483 388 420 452 484 389 421 453 485 390 422 454 486 391 423 455 487 392 424 456 488 393 425 457 489 394 426 458 490 395 427 459 491 396 428 460...

Страница 101: ...2 513 545 577 609 514 546 578 610 515 547 579 611 516 548 580 612 517 549 581 613 518 550 582 614 519 551 583 615 520 552 584 616 521 553 585 617 522 554 586 618 523 555 587 619 524 556 588 620 525 5...

Страница 102: ...odule Point No Type of Device Output Module 641 673 642 674 643 675 644 676 645 677 646 678 647 679 648 680 649 681 650 682 651 683 652 684 653 685 654 686 655 687 656 688 657 689 658 690 659 691 660...

Страница 103: ...on the CPU 640 and TB1 terminals 3 and 4 on the UDACT being certain to observe polarity If no other devices are connected to the EIA 485 install a 120 ohm EOL resistor across UDACT TB1 terminals 3 and...

Страница 104: ...URE 24V 24V GND RS RS SHIELD RS Rs ACS TERM TERM To Phone Lines supervised Solid Earth Ground Connection ABS 8R or UBS 1 NFS 640 in Separate Cabinet CPU 640 TB13 UDACT 13a cdr DO NOT USE Ferrite Cores...

Страница 105: ...are programmed by Type Mode Entries Addresses 449 512 Loop 2 Detectors 65 128 are programmed by Type Mode Entries Addresses 513 576 Event Code Report Transmission Via Ademco Contact ID Format Only Fo...

Страница 106: ...Event Code Report Transmission 106 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...

Страница 107: ...d 4 on the UDACT being certain to observe polarity If no other devices are connected to the EIA 485 install a 120 ohm EOL resistor across UDACT TB1 terminals 3 and 4 Connect the Ground Wire PN 71073 p...

Страница 108: ...t NOTE Use Table 51 and in Appendix I AM2020 AFP1010 as worksheets for the NCA EARTH Comm FAILURE 24V 24V GND RS RS SHIELD RS Rs ACS TERM TERM To Phone Lines supervised Solid Earth Ground Connection A...

Страница 109: ...he control panel by disconnecting AC and batteries before making any connections to prevent personal and or circuit damage Connections Refer to Figure 29 and Figure 30 on page 110 Connect the communic...

Страница 110: ...MPS 24B EARTH Comm FAILURE 24V 24V GND RS RS SHIELD RS Rs ACS TERM TERM 24R COMMON 24 COMMON POWER LIMITED BAT BAT To Phone Lines supervised Solid Earth Ground Connection MPS 24A SIB 2048 EIA 485 Int...

Страница 111: ...unction Point No Point Function Point No Point Function 001 051 101 151 002 052 102 152 003 053 103 153 004 054 104 154 005 055 105 155 006 056 106 156 007 057 107 157 008 058 108 158 009 059 109 159...

Страница 112: ...363 214 264 314 364 215 265 315 365 216 266 316 366 217 267 317 367 218 268 318 368 219 269 319 369 220 270 320 370 221 271 321 371 222 272 322 372 223 273 323 373 224 274 324 374 225 275 325 375 226...

Страница 113: ...560 411 461 511 561 412 462 512 562 413 463 513 563 414 464 514 564 415 465 515 565 416 466 516 566 417 467 517 567 418 468 518 568 419 469 519 420 470 520 421 471 521 422 472 522 423 473 523 424 474...

Страница 114: ...Point Assignments 114 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...

Страница 115: ...CAUTION Remove all power from the control panel by disconnecting AC and batteries before making any connections to prevent personal and or circuit damage Connections Refer to Figure 31 on page 116 Co...

Страница 116: ...24 E UDACT 15 cdr CAB 3 4 Series Cabinet To supervised phone lines Solid earth ground EIA 485 ACS Mode TB7 on control panel 24V Gnd RS RS Shield RS RS ACS Term TERM NC 24 VDC non resettable power TB6...

Страница 117: ...o Point Function Point No Point Function Point No Point Function 001 051 101 151 002 052 102 152 003 053 103 153 004 054 104 154 005 055 105 155 006 056 106 156 007 057 107 157 008 058 108 158 009 059...

Страница 118: ...363 214 264 314 364 215 265 315 365 216 266 316 366 217 267 317 367 218 268 318 368 219 269 319 369 220 270 320 370 221 271 321 371 222 272 322 372 223 273 323 373 224 274 324 374 225 275 325 375 226...

Страница 119: ...0 460 510 560 411 461 511 561 412 462 512 562 413 463 513 563 414 464 514 564 415 465 515 565 416 466 516 566 417 467 517 567 418 468 518 568 419 469 519 420 470 520 421 471 521 422 472 522 423 473 52...

Страница 120: ...Point Assignments 120 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...

Страница 121: ...batteries before making any connections to prevent personal and or circuit damage Connections Refer to Figure 33 and Figure 34 on page 122 Connect the communication line between the EIA 485 terminal b...

Страница 122: ...ith MPS 24B EARTH Comm FAILURE 24V 24V GND RS RS SHIELD RS Rs ACS TERM TERM 24R COMMON 24 COMMON POWER LIMITED BAT BAT To Phone Lines supervised Solid Earth Ground Connection MPS 24A INA DO NOT USE UD...

Страница 123: ...nt With UDACT 1 System Trouble except AC loss System Trouble except AC loss 2 Signals Silenced Signals Silenced 3 Not Used Program Mode 4 Not Used Supervisory 5 Supervisory Bell Trouble 6 Prealarm Pre...

Страница 124: ...a UDACT with the AM2020 AFP1010 INA the first Red LED on an annunciator is used to annunciate alarms while LEDs 2 through 8 are not used Yellow Annunciator LED Assignment Without UDACT Assignment With...

Страница 125: ...l 9 Installation Options 19 panel ID 34 schematic 86 AFP 400 25 62 AFP4R20 11 AIM mode 79 AIM 200 33 62 79 Alarm Code 37 38 AM2020 device zone number 35 multiple 35 AM2020 AFP1010 25 33 62 annunciator...

Страница 126: ...95 105 factory programmed 53 fault detection of 52 on EIA 485 51 Fault Code 37 38 fault conditions 50 fault events 50 fault message 54 FBI 65 Features 10 Ferrite cores 68 71 75 80 85 93 103 107 109 1...

Страница 127: ...9 NFS 3030 AMPS 24 schematic 116 NFS 640 25 33 62 103 Firmware 11 Installation Options 19 panel ID 34 Schematic 104 NFS 640 Installation Manual 9 nonpower limited 27 Normal Mode 15 29 36 49 52 54 57...

Страница 128: ...ual 9 panel ID 34 schematic 76 System 5000 25 33 62 addresses 87 Annunciators 123 Firmware 11 Installation Options 19 Instruction Manual 9 panel ID 34 schmatic 81 System 5000 AIM 33 62 panel ID 34 T t...

Страница 129: ...PN 50050 H 09 16 2002 129 W wiring entering 27 exiting 27 nonpower limited 27 power limited 27 Relay Driver 25 Z zone 33 59 62 zone number 55 zone reporting 33 34 zone trouble 25 Technical Manuals Onl...

Страница 130: ...130 UDACT Instruction Manual PN 50050 H 09 16 2002 Technical Manuals Online http www tech man com...

Страница 131: ...NOTIFIER 12 Clintonville Road Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products w...

Страница 132: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www notifier com NOTIFIER is an operation of Technical Manuals Online http www tech man com...

Отзывы: