Detector Status Display
AWACS™ Applications
NFS-3030 Programming Manual P/N 51345:C 11/4/03
111
How to Test Detectors Set Below 0.50% Obscuration per Foot
Using alarm sensitivities below 0.50% obscuration per foot requires a 90-day test to ensure that the
detector environment is suitable for the higher sensitivity setting. To meet Notifier and
Underwriters Laboratory requirements, test each detector planned to operate below 0.50%/ft
obscuration as follows:
4. Set the detector as follows:
5. Operate detectors continuously for 90 days with all environmental factors (such as,
temperature, humidity, air flow, occupancy, and so on) similar to the intended application for
the detectors. Record all events for each tested detector with an electronic History buffer or a
printout.
6. At the end of the 90-day test: An authorized Notifier representative, or an end user trained by
an authorized Notifier representative must inspect the results of the test. If the test results show
no alarms or pre-alarms for the tested detectors, reprogram the fire alarm system to set the
Alarm sensitivity to the more sensitive Pre-Alarm level of the test.
D.5 Detector Status Display
Detector Maintenance Display
Should the panel detect a low chamber value or maintenance condition with a detector, it will
generate a point trouble as described in the operations manual for this panel. The following Read
Status screen displays detector information that applies to the state of the smoke detector. It can be
reached with the following commands, starting at the Main Menu screen:
Press
MAIN MENU
Press
READ STATUS
Press
READ STATUS POINT SELECT
(enter the detector point address)
Press
ACCEPT
Appendix Figure D-6 Smoke Detector Screen - Read Status
Step
Action
1
Initially set to the 0.50% obscuration per foot Alarm level.
2
Set the Pre-Alarm level to the desired final Alarm sensitivity.
3
Set the Pre-Alarm to Alert mode (non-latching).
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I J U L 1 9 , 2 0 0 2
R E A D A D D R E S S :
L 0 3 D 0 5 2
A U T O M A T I C
I N A C T I V E
E L E V A T O R L O B B Y
E A S T W I N G
F I F T H F L O O R
Z 0 0 3
S M O K E ( P H O T O )
Z 0 0 5 ,
Z 0 2 7 ,
Z 0 6 6 ,
,
,
,
,
,
,
,
V A L U E S : 0 1 1 % O F A L A R M , 0 4 5 % O F P R E A L A R M
A L A R M : 6 = 1 . 6 6 % , P R E A L A R M : 3 = 0 . 4 7 %
A C T I O N / S T A T U S : N O N E / V E R Y C L E A N
P E A K S : 5 6 % V E R I F Y C O U N T : 0 2 C O - O P : D 1 0 0 , 1 5 8
1 0 : 2 2 : 3 4 A
F R I J U L 1 9 , 2 0 0 2
B A C K
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...