Releasing Applications
Abort Switches
86
NFS-3030 Programming Manual P/N 51345:C 11/4/03
AHJ Abort Switch
An AHJ (Authority Having Jurisdiction) Abort Switch has a delay timer that restores the
programmed Delay Time.
Note: An AHJ timer does not comply with UL Standard 864.
When an alarm initiates in the programmed releasing zone, the programmed Delay Time starts.
Pressing and holding the abort switch suspends the delay timer. When the abort switch is released,
the control panel restores the value of the programmed Delay Time and the delay timer counts
down. When the Delay Time expires, the control panel activates releasing zone outputs.
Appendix Figure B-8 AHJ Abort Switch
Delay Time: 60 seconds
Abort Switch: AHJ
Cross Zone: N
Soak Time: 0
Program selections for this releasing zone
Release the abort switch and the control
panel restores the programmed value
Delay Time (60 sec.) and counts down
Delay=60 sec.
Press and hold
the Abort Switch
(30 sec.)
When the Delay Time
expires, the control panel
activates releasing zone
outputs
30 sec.
45 sec.
60 sec.
Total time from alarm initiation to release:
45 + 30 + 60 = 135 seconds
Alarm
0 sec.
45 sec
60 sec.
75 sec.
135 sec.
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...