Basic Procedure
General Information
NFS-3030 Programming Manual P/N 51345:C 11/4/03
11
screen.
When the FACP can not read an address (that is, if the point entered on the screen for processing
does not exist) it will display an error screen for several seconds, then return to the screen where the
address was entered. The user must check his input and investigate the state of the point.
1.5 Basic Procedure
For initial programming of the panel, or for major changes and additions, the following basic
procedure is recommended to prevent errors resulting in reprogramming and wasted time.
•
Use work sheets to record the exact information for every detector, module, annunciator point
and software zone in the system. Pay close attention to the Software Type IDs. For voice
systems, pay close attention to AMG annunciator point commands. The panel program may
also be created using VeriFire™ Tools and downloaded to the panel after assembly and power-
up.
•
Assemble and apply power to the control panel as described in this panel’s installation manual.
All system boards must be physically installed.
•
Read this manual before programming.
•
Enter/change master and user passwords.
•
Enter panel and network parameters.
•
Program all devices and thoroughly test the entire system. The Walk Test feature can be used to
test devices and their programming.
•
Make a hard-copy record of the program on the printer.
•
Save the program by uploading it using VeriFire™ Tools.
1.6 Getting Started
Once the system has been physically installed, programming may begin. The user may program at
any time except while there is an unacknowledged alarm present.
To ensure security, passwords should be entered at this time to replace the factory default settings.
1.6.1 Password Change
The NFS-3030/E has two password levels; master and user. There is one master password, which
grants access to all system programming. There are nine user passwords, each of which may be
assigned access to the programming change menus, the alter status menus, or both. A user
password does not give access to or allow change to any password parameters, not even its own.
Only the master password will allow access to password change screens.
The panel arrives with factory default settings of 00000000 for the master password, and 11111111
for one user password.
Follow the steps below to change the factory settings:
1. Press
PROGRAM/ALTER
STATUS
at the Main Menu screen.
2. Using the keyboard, enter eight zeroes (00000000) after
ENTER
PASSWORD
.
3. Press the
ACCEPT
soft key.
4. Press the
PANEL
PROGRAM
MENU
soft key.
5. Press the
MORE
soft key.
6. Press the
PASSWORD
CHANGE
soft key.
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...