Panel Program
Program
NFS-3030 Programming Manual P/N 51345:C 11/4/03
19
NODE LABEL:
Enter the network node label for this panel. This is the label that appears in the
System Normal message. Default: <blank>
STYLE:
Select the wiring style as 4 or 7. Default: style 4
CHANNEL
A
THRESHOLD, CHANNEL
B
THRESHOLD:
Enter
HIGH
or
LOW
, for high or low
threshold setting for channel A or B on the NCM module. Default:
HIGH
ACCEPT:
Press this soft key to save the information entered on this screen.
3.2.3 Panel Settings
Press the Panel Settings soft key on the Panel Program Menu 1 screen to choose panel settings.
Figure 3.4 Panel Settings (1) Screen
Soft Keys
LOCAL
CONTROL:
Press this soft key to toggle between Yes and No. This option disables (No) or
enables (Yes) local panel control of the Signal Silence, System Reset, and Drill Fixed Function
keys, as well as
SIGNAL
SILENCE
,
SYSTEM
RESET
, and
ACKNOWLEDGE
soft keys. A setting of
No (disable) turns the panel piezo sounder off, overriding the next field if
PIEZO
is set to ON.
Default: Yes
Note: A setting of NO (disable) will disable key switch operation.
Note: ACS devices programmed for acknowledge, signal silence, system reset and drill are not affected by
this setting: these commands will still function at the devices if
LOCAL
CONTROL
is set to No.
PIEZO:
Press this soft key to toggle between Off and On. This option enables (On) or disables
(Off) the panel piezo from sounding when alarms or troubles occur. A setting of On is overridden if
LOCAL
CONTROL
is set to No. Default: On
PROPRIETARY
SUPERVISING
STATION:
Press this soft key to enable (Yes) or disable (No)
Local Receive mode. When enabled, events and the clearing of events must be handled one at a
time: each must be acknowledged. Latching events require a system reset. The panel will override a
setting of Yes if the Node Number is greater than zero. Default: No
EVENT
ORDERING:
Press this soft key to toggle between USA and Canada ordering priorities.
This order is applied to events shown in the Multiple Events List screen. Default: USA
USA Event Order
Canada Event Order
Fire
Fire
Security
Supervisory
Supervisory
Trouble
Trouble
Prealarm
Prealarm
Disabled
Disabled
P A N E L S E T T I N G S
L O C A L C O N T R O L : Y E S
R E M I N D E R M E N U
P I E Z O : O N
M O R E
P R O P R I E T A R Y S U P E R V I S I N G S T A T I O N : N O
E V E N T O R D E R I N G : U S A
A C C E P T
D I S P L A Y A D D R E S S : Y E S
B A C K
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...