Releasing Applications
Abort Switches
88
NFS-3030 Programming Manual P/N 51345:C 11/4/03
Each Cross Zone option and the conditions required to activate releasing zone ZR01 are shown in
the table below, according to the example in Appendix Figure B-9.
Using Type Codes for Releasing Zones
The control panel provides a set of Type Codes designed for releasing applications for inputs and
outputs. This section details how to program each of these Type Codes.
Note: Panel circuit modules are not suitable for the release of agents.
Type Codes designed for releasing zone
inputs
(SLC monitor modules).
Type Codes designed for releasing zone
outputs
(SLC control modules).
Cross Zone
Selection (Cross=)
Condition(s) Required to Activate the Releasing zone
Cross=
No
An alarm from any initiating device activates the releasing zone.
Cross=
Yes
An alarm from any two initiating devices activates the releasing zone.
Cross=
Zone
For example:
An alarm from two initiating devices mapped to different primary
general zones, but mapped to the same releasing zone.
• An alarm from L02D101 and L02D103
• An alarm from L02D102 and L02D104
• An alarm from L02D101 and L02D104
• An alarm from L02D102 and L02D103
The two detectors listed in each set above are each mapped to different
primary general zones, but both list ZR01 in their zone maps.
Cross=
Heat
Activation of heat detector L02D104 and one smoke detector
(L02D101, L02D102, or L02D103).
Type Code
What the Type Code does
Refer to
ABORT
SWITCH
(tracking)
Provides an abort function through
a monitor module (connected to a
UL-listed abort station) for a
releasing zone.
"How to Program an Abort
Switch" on page 90
MAN
.
RELEASE
(latching)
Provides a manual release through
a monitor module (connected to a
UL-listed pull station) for a
releasing zone.
"How to Program a Manual
Release Switch" on page 91
MAN
REL
DELAY
(latching)
Provides a manual release with a
10-second delay through a monitor
module (connected to a UL-listed
pull station) for a releasing zone.
"How to Program a Manual
Release Delay Switch" on page 92
SECOND
SHOT
(latching)
Provides a second manual release
through a monitor module
(connected to a UL-listed pull
station) for a releasing zone.
"How to Program a Second Shot
Switch" on page 94
Type Code
What the Type Code does
Refer to
REL
END
BELL
Activates an NAC audio or visual
device when releasing circuits shut
off.
"How to Program a Release End
Bell Circuit" on page 95
REL
CKT
ULC
Directs outputs to perform a release
function as required by ULC.
"How to Program a ULC Release
Circuit" on page 96
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...