Appendix F: Detector Initialization
F.1 Overview
The control panel automatically performs a detector initialization routine when a detector is added
or changed.
The detector initialization routine takes approximately 2.5 minutes. During this time, the detector
being initialized does not perform fire protection functions. The LEDs of detectors polled in
FlashScan mode will latch a steady green while initializing, and return to blinking green when
initialization is over.
While initializing a detector, follow these guidelines:
•Make sure the detector is free of residual smoke during detector initialization.
•Do not test a detector during detector initialization.
Note: The control panel only performs detector initialization if it senses that a detector was removed for at least
15 seconds.
WARNING: If any detector is replaced with a different type of detector (for example, a laser
detector is replaced with a photoelectric detector), the control panel must be programmed
immediately with the new detector Type Code. Failure to do so can cause incorrect control
panel operation, including false alarms.
F.2 How to Replace a Detector with a Different Type of Detector
If one type of detector is replaced with a different type of detector, the control panel must
immediately be programmed for the new detector type. To replace a detector, follow these steps:
Step
Action
1
Delete the old detector point from FACP programming using the “Delete Point” screen on
page 53.
2
Physically remove the old detector.
3
Enter point programming for this point and change the Type and FlashScan Code Label to
the values appropriate for the new detector. (Refer to “Detector Point” on page 35 for
programming instructions).
4
Physically install the new detector. Initialization will occur automatically
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...