Program
Panel Program
26
NFS-3030 Programming Manual P/N 51345:C 11/4/03
Note: Panel circuit or SLC output modules with releasing Type IDs may not be listed in the
annunciator source fields.
Figure 3.11 ACS Point Programming Screen
Soft Keys
POINT:
Press this soft key to enter the ACS point number. The format is AxxPyy, where A is the
two-digit device address, P is the two-digit point number. Enter a leading zero for one-digit
numbers.
MODE:
Press this soft key to enter the ACS mapping mode. Refer to the following chart for
possible mode choices and descriptions of their functions.
A C S P O I N T P R O G R A M M I N G
P O I N T :
A 2 7 P 0 4
M O D E :
C O N T R O L
S O U R C E : L 0 1 M 0 3 7
L 0 1 M 0 3 8
P 1 0 . 2
N E X T
A C C E P T
P R E V I O U S
B A C K
ACS Point
Mode
Function
The point...
Explanation
None
is not programmed.
No messages are sent from or received at this point. LEDs at this point do
not light.
Control
will change the state of up to eight panel
circuits or control modules to off or on when its
button is pushed.
The Point Active LED is lit if a corresponding mapped point is active. The
Status (trouble) LED is on when a point or zone is disabled or in trouble.
This mode is not for use with an ACS point with no switch, or with a TM-4
or UDACT.
Monitor
will show the current status of a specified point
or zone.
The Point Active LED is lit if the corresponding mapped point or zone is
active. The Status (trouble) LED is on if that point or zone is disabled or in
trouble. If the point has a button, it has no effect when pushed.
Telephone
supports telephone functionality when mapped
to a telephone point. Press the button to
connect the mapped point with the telephone
station.
Both the Point Active LED and the Status (trouble) LED will flash if a
telephone has been placed in the jack at the mapped telephone point.
Otherwise, the Point Active LED is lit if the corresponding point or zone is
active. The Status (trouble) LED is lit if that point or zone is in trouble or
disabled.
This mode is for use with ACS Series annunciator points configured for
telephone operation.
Disable
will change the state of a point or zone
specified through mapping from enabled to
disabled, or from disabled to enabled, when its
button is pushed.
The Point Active LED is lit if the corresponding mapped point or zone is
active. The Status (trouble) LED is lit if that point or zone is disabled or in
trouble.
This mode is not for use with an ACS point with no switch, or with a TM-4,
UDACT, or smoke control device.
Acknowledge
will act like an Acknowledge soft key or button
on the panel, acknowledging an event when its
button is pushed.
The Point Active LED is lit when there are any fire alarms in the system.
The Status (trouble) LED is lit when there are troubles in the system.
Silence
will act like the Signal Silence button on the
panel, silencing all silenceable outputs when
its button is pushed.
The Point Active LED is lit if all silenceable outputs have been silenced.
The Status (trouble) LED is lit if not all silenceable outputs have been
silenced after the button is pushed.
Reset
will act like the System Reset button on the
panel, resetting the panel when its button is
pushed.
No LED will ever light at this point.
This mode is not for use with an ACS point with no switch, or with a TM-4,
UDACT, or smoke control device.
Drill
will act like the Drill button on the panel,
initiating a fire drill when its button is pushed.
The Point Active LED lights when the button is pushed and the system has
entered the drill state. The Status (trouble) LED will never light.
This mode is not for use with an ACS point with no switch, or with a TM-4,
UDACT, or smoke control device.
www.PDF-Zoo.com
Содержание NFS-3030/E
Страница 14: ...General Information Getting Started 14 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 76: ...Service Screens Application Corrupt Screen 76 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 120: ...CBE Zones and Equations Equations 120 NFS 3030 Programming Manual P N 51345 C 11 4 03 Notes www PDF Zoo com...
Страница 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Страница 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...