2.8 Generator Winding Connections

Figure 01175 represents a simplified pictorial of
the generator stator AC connection system. This
sy stem is described as a 60-Hertz, single phase,
four-wire design. The generator  stator  produces
120/240 volts by means of two independent
stationary coil groups (windings), with two leads
brought out of each winding. Each winding can
nominally produce 120 Volts at 60 Hertz.
Combining both windings in series produces 240
Volts at 60 Hertz. Generator output leads 1 and 4
are ”HOT”. Generator output leads 2 and 3 are
“Neutral”.

Fig. 01175 - Generator AC Connection System

2.9 Wiring Connections

   

DANGER 

 Qualified electricians or

contractors should complete the wiring
connections.  Follow  all applicable  electrical
codes, regulations, and standards.

 

CAUTION 

  Customer installed w ires

designated as “pow er” lead should not be
mixed with “signal” leads  in  the same
electrical conduit.

 

CAUTION 

 The generator is configured

w ith a ‘bonded neutral” wire. The neutral w ire
exiting the generator is bonded to the ground
circuit.

 

DANGER

 

 

Always 

disconnect the  battery

prior to installation or  servicing  the generator  or
transfer switch. 

This product can start

automatically

. Disconnect the battery cable from  the

NEGATIVE, NEG, or (-) terminal first. Reconnect that
cable last.

 

DANGER

 

 

Never 

work inside the generator

unless utility power is disconnected. 

Remember

: The

battery charger and convenience receptacle may be
energized by a 120-volt electrical circuit that is
independent of the stand-by generator.

This generator is designed with  a 3.25”  diameter
hole in the base. This access hole allows for
routing of electrical conduit up through  the
concrete mounting pad and into  the generator
housing. See Figure 01168 (page 8).   If  the
installation does not allow the conduit to route
through the concrete pad, see the Right Side  View
of Figure 01165 (page 7) for the area  to locate
conduit elbows.

To complete the electrical connections, first
remove the (4) #10 socket head cap screws from
the lower cover plate. The #10 socket head cap
screws can be removed with a  5/32” hex  key.  See
Figure 01186.

Fig. 01186 - Generator Control Box

#10 SOCKET HEAD
CAP SCREWS

LOWER

COVER

PLATE

Содержание 10500 SBG

Страница 1: ...0500 SBG Stand By Generator Installation and Operation Manual DANGER ONLY A QUALIFIED CONTRACTOR OR ELECTRICIAN SHOULD INSTALL THIS PRODUCT IT MUST BE INSTALLED IN ACCORDANCE WITH APPLICABLE REGULATIO...

Страница 2: ...ator Observe the DANGER WARNING and CAUTION blocks carefully Their definitions are as follows DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious in...

Страница 3: ...ES ELECTRICAL HAZARDS The generator covered within this manual can and will produce dangerous electrical voltages that cause fatal electrical shocks The utility power that is connected to the transfer...

Страница 4: ...ness Page 21 Electrical Schematic Page 22 Stand By Generator Parts Explosion Page 23 24 Fuel System Parts Explosion Page 25 26 Control Panel Wiring Diagram Page 27 28 Section 1 Specifications 1 1 Engi...

Страница 5: ...hone book under the classification Electrical Contractors Heating and A C Contractors Look in your local phone book under the classification Heating Contractors or Air Conditioning Contractors Call Cu...

Страница 6: ...to the collection of rainwater 2 Never install the generator in an area that is prone to flooding 3 Never locate the generator on a roof 4 Always locate the generator as close to the transfer switch...

Страница 7: ...6 FIG 01165 GENERATOR DIMENSIONS...

Страница 8: ...7 FIG 01168 Mounting Pad Design...

Страница 9: ...FM 9 33 lb hr 2 2 gal hr BTU HR 161374 201718 2 7 Fuel System Components The fuel system is composed of four main components fuel lock off demand regulator load block and carburetor adapter See Figure...

Страница 10: ...exiting the generator is bonded to the ground circuit DANGER Always disconnect the battery prior to installation or servicing the generator or transfer switch This product can start automatically Disc...

Страница 11: ...ulation removed prior to insertion into the connection lug A lead wire that is inserted into a compression connection without adequate insulation removed may create an open circuit Inside most transfe...

Страница 12: ...URB LOCATION DIN RAIL CONNECTION LUGS 35 IN LBS TORQUE EXTERNAL ELECTRICAL CIRCUIT TO POWER THE GFCI RECEPTACLE AND BATTERY CHARGER HOT LEAD WIRE 120V CIRCUIT NEUTRAL LEAD WIRE GROUND LEAD WIRE LEAD W...

Страница 13: ...A C with a current rating of 20 Amps The GFCI receptacle accepts either NEMA 5 15P or NEMA 5 20P electrical plugs A 125 volt 20 amp circuit breaker protects the GFCI receptacle If the circuit breaker...

Страница 14: ...s designed to operate on either Liquid Propane Gas LPG or Natural Gas NG The fuel system was factory set for NG If the engine will not start starts poorly or requires conversion to LPG it may be neces...

Страница 15: ...mixture of 1 pound of bicarbonate of soda to 1 gallon of water The resulting solution is to be applied to the acid spill until evidence of reaction foaming has ceased Rinse the entire area with tap w...

Страница 16: ...e battery The positive battery charger cable is colored RED and is labeled There is also an inline fuse and fuse holder associated with the RED battery charger lead The negative battery charger cable...

Страница 17: ...ug prevents accidental loss of engine oil A 5 16 hex key Allan Wrench is required to remove the oil drain plug Reference 8 Engine Oil Drain Valve The engine oil drain valve provides a convenient metho...

Страница 18: ...meter provides a convenient way to monitor oil change intervals Reference 21 System Controller The system controller starts stops and monitors the generator set There are five alarm lamps associated...

Страница 19: ...lead wire 01A the three position switch closes a circuit between lead wires 06A and 07 The closure of lead wires O6A and O7 tells the system controller to send 12 volts dc to the engine start solenoid...

Страница 20: ...ia the two lead wires O10 and O11 Trouble Shooting Hint The system control board will shut down the engine if lead wires O10 and O11 are connected together If the thermo disk is closed lead wires O10...

Страница 21: ...enerator set and any underground gas piping Defective fuel lock off solenoid Check that 12 volts dc is present at solenoid Load block not set properly Readjust load block set screw See Section 2 10 Fu...

Страница 22: ...21...

Страница 23: ...22...

Страница 24: ...23...

Страница 25: ...8 25 19 34867 Patch Plate Weldment 1 20 32839 Positive Battery Cable 1 21 777108 Negative Battery Cable 1 22 34589 Engine Voltage Regulator 1 23 35011 Grommet 1 24 36749 Battery Charger 1 25 34873 Bas...

Страница 26: ...25...

Страница 27: ...ter Cap 1 14 35008 O Ring 1 15 82187 M6 1 0 x 70 mm Socket Head Cap Screw w patch 2 16 35037 Air Cleaner Riser 1 17 34242 High Temp Switch 1 18 34851 High Temp Bracket 1 19 36774 Honda 20 HP Engine 1...

Страница 28: ...27...

Страница 29: ...tch 1 10 30643 20A Thermal Circuit Breaker 1 11 31344 20A Receptacle 1 12 36750 End Bracket 2 13 305539 40A Circuit Breaker 1 14 36820 Terminal Block 1 15 36755 Grounding Terminal Block 1 16 36753 Ter...

Отзывы: