2.9.3 Automatic Start Connections

This generator is equipped with a automatic
engine start feature. If it is desired to enable this
feature, the Auto/Off/Manual selector switch
(Figure 01199) is located on the control panel and
must be in the Auto position. The generator will
then start when terminals #5 and #6 (Figure
01192) are connected to a remote set of contacts.
The remote contacts must be configured as such:

close

 

to start the engine

, and 

open to stop the

engine

. Generally, all transfer switches have a set

of remote engine start contacts. These contacts
close upon loss of utility power, and open once
utility power is restored. If your transfer switch is a
General Electric ZTX100 (Northern Tool &
Equipment item #165969) or General Electric
ZTX200 (Northern Tool & Equipment item #
165970) the engine start contacts are labeled as
X1 and X2 inside the transfer switch enclosure.
Refer to your Transfer Switch owners’ manual for
further information.

2.10 Fuel Mixture Reconfiguration

This generator set is designed to operate on  either
Liquid Propane Gas (LPG) or Natural Gas (NG).
The fuel system was factory set for NG. If the
engine will not start, starts poorly, or requires
conversion to LPG, it may be necessary to adjust
the fuel mixture. To adjust the fuel mixture, locate
the fuel regulator assembly (Figure 01201). The
following tools are required to reconfigure the fuel
mixture: (1) 11/16”  open-end  wrench and  (1)
straight blade screw driver.

Fig. 01201 - Regulator Assembly

The load block adjusts the fuel mixture that is fed into
the carburetor.  To adjust  the load block,  loosen  the
lock nut. The adjustment screw now  can be turned
either clockwise or counter clockwise. While LPG or
NG is supplied to the fuel  connection point  (Figure
01174) put the Auto/Off/Manual selector switch in the
Manual position (Figure 01199)  and  slowly turn the
adjustment screw clockwise until the engine starts
(Figure 01202). Once the engine is running turn the
adjustment screw very slowly to  smooth  out engine
performance. Once the proper setting is  achieved  turn
the brass lock nut to secure the adjustment screw.

               Fig. 01202 - Load Block Adjustment

FUEL REGULATOR ASSEMBLY

ADJUSTMENT

SCREW

SCREW
DRIVER

11/16” WRENCH

DEMAND
REGULATOR

Содержание 10500 SBG

Страница 1: ...0500 SBG Stand By Generator Installation and Operation Manual DANGER ONLY A QUALIFIED CONTRACTOR OR ELECTRICIAN SHOULD INSTALL THIS PRODUCT IT MUST BE INSTALLED IN ACCORDANCE WITH APPLICABLE REGULATIO...

Страница 2: ...ator Observe the DANGER WARNING and CAUTION blocks carefully Their definitions are as follows DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious in...

Страница 3: ...ES ELECTRICAL HAZARDS The generator covered within this manual can and will produce dangerous electrical voltages that cause fatal electrical shocks The utility power that is connected to the transfer...

Страница 4: ...ness Page 21 Electrical Schematic Page 22 Stand By Generator Parts Explosion Page 23 24 Fuel System Parts Explosion Page 25 26 Control Panel Wiring Diagram Page 27 28 Section 1 Specifications 1 1 Engi...

Страница 5: ...hone book under the classification Electrical Contractors Heating and A C Contractors Look in your local phone book under the classification Heating Contractors or Air Conditioning Contractors Call Cu...

Страница 6: ...to the collection of rainwater 2 Never install the generator in an area that is prone to flooding 3 Never locate the generator on a roof 4 Always locate the generator as close to the transfer switch...

Страница 7: ...6 FIG 01165 GENERATOR DIMENSIONS...

Страница 8: ...7 FIG 01168 Mounting Pad Design...

Страница 9: ...FM 9 33 lb hr 2 2 gal hr BTU HR 161374 201718 2 7 Fuel System Components The fuel system is composed of four main components fuel lock off demand regulator load block and carburetor adapter See Figure...

Страница 10: ...exiting the generator is bonded to the ground circuit DANGER Always disconnect the battery prior to installation or servicing the generator or transfer switch This product can start automatically Disc...

Страница 11: ...ulation removed prior to insertion into the connection lug A lead wire that is inserted into a compression connection without adequate insulation removed may create an open circuit Inside most transfe...

Страница 12: ...URB LOCATION DIN RAIL CONNECTION LUGS 35 IN LBS TORQUE EXTERNAL ELECTRICAL CIRCUIT TO POWER THE GFCI RECEPTACLE AND BATTERY CHARGER HOT LEAD WIRE 120V CIRCUIT NEUTRAL LEAD WIRE GROUND LEAD WIRE LEAD W...

Страница 13: ...A C with a current rating of 20 Amps The GFCI receptacle accepts either NEMA 5 15P or NEMA 5 20P electrical plugs A 125 volt 20 amp circuit breaker protects the GFCI receptacle If the circuit breaker...

Страница 14: ...s designed to operate on either Liquid Propane Gas LPG or Natural Gas NG The fuel system was factory set for NG If the engine will not start starts poorly or requires conversion to LPG it may be neces...

Страница 15: ...mixture of 1 pound of bicarbonate of soda to 1 gallon of water The resulting solution is to be applied to the acid spill until evidence of reaction foaming has ceased Rinse the entire area with tap w...

Страница 16: ...e battery The positive battery charger cable is colored RED and is labeled There is also an inline fuse and fuse holder associated with the RED battery charger lead The negative battery charger cable...

Страница 17: ...ug prevents accidental loss of engine oil A 5 16 hex key Allan Wrench is required to remove the oil drain plug Reference 8 Engine Oil Drain Valve The engine oil drain valve provides a convenient metho...

Страница 18: ...meter provides a convenient way to monitor oil change intervals Reference 21 System Controller The system controller starts stops and monitors the generator set There are five alarm lamps associated...

Страница 19: ...lead wire 01A the three position switch closes a circuit between lead wires 06A and 07 The closure of lead wires O6A and O7 tells the system controller to send 12 volts dc to the engine start solenoid...

Страница 20: ...ia the two lead wires O10 and O11 Trouble Shooting Hint The system control board will shut down the engine if lead wires O10 and O11 are connected together If the thermo disk is closed lead wires O10...

Страница 21: ...enerator set and any underground gas piping Defective fuel lock off solenoid Check that 12 volts dc is present at solenoid Load block not set properly Readjust load block set screw See Section 2 10 Fu...

Страница 22: ...21...

Страница 23: ...22...

Страница 24: ...23...

Страница 25: ...8 25 19 34867 Patch Plate Weldment 1 20 32839 Positive Battery Cable 1 21 777108 Negative Battery Cable 1 22 34589 Engine Voltage Regulator 1 23 35011 Grommet 1 24 36749 Battery Charger 1 25 34873 Bas...

Страница 26: ...25...

Страница 27: ...ter Cap 1 14 35008 O Ring 1 15 82187 M6 1 0 x 70 mm Socket Head Cap Screw w patch 2 16 35037 Air Cleaner Riser 1 17 34242 High Temp Switch 1 18 34851 High Temp Bracket 1 19 36774 Honda 20 HP Engine 1...

Страница 28: ...27...

Страница 29: ...tch 1 10 30643 20A Thermal Circuit Breaker 1 11 31344 20A Receptacle 1 12 36750 End Bracket 2 13 305539 40A Circuit Breaker 1 14 36820 Terminal Block 1 15 36755 Grounding Terminal Block 1 16 36753 Ter...

Отзывы: