17
3.1 Control Box Components
START SW I TCH
OFF
RESET
HOUR MET ER
AUT O
10500 SBG
S TA NDB Y GENE RA TOR
70
Reference 16: Main Line Circuit Breaker
. The
main circuit breaker is a 2-pole design that
protects the generator from electrical overloads. If
the circuit breaker trips, reset the breaker by
moving the lever to the OFF position and then
back to the ON position.
Reference 17: ON/OFF/AUTO
. This switch will
start the engine if placed in the ON position. When
the switch is in the AUTO position, the generator
will start when the transfer switch senses loss of
utility power. The OFF position shuts down the
engine.
WARNING
•
With the sw itch set in the
AUTO position, the engine can crank and start
w ithout w arning. Automatic starting can occur
w ith loss of normal utility pow er or during a
normal exercise initiated by the transfer
sw itch. To prevent accidental engine starting,
place the switch in the OFF position and
disconnect the battery prior to w orking on or
around the generator.
Reference 18: Maintenance Interv al Reset
Sw itch
. The maintenance interval meter can be
instantly reset to zero by depressing the switch.
Reference 19: Total Hour Meter
. The total hour
meter measures hours the engine has
accumulated while running. This portion of the
meter cannot reset.
Reference 20: Maintenance Interv al Meter
.
The lower meter is a maintenance interval meter.
It is used to measure hours between scheduled
maintenance. To reset this meter, depress the
maintenance interval reset switch (Reference 18).
This meter provides a convenient way to monitor
oil change intervals.
Reference 21: System Controller
. The system
controller starts, stops, and monitors the generator
set. There are five alarm lamps associated with
the engine controller. Their functions are as
follows:
Low Oil Pressure-
In the event of low engine oil
pressure, the “low oil pressure” lamp will glow red,
and the engine will shut down. To reset the system
controller, place the ON/OFF/AUTO switch in the
OFF position. Check the engine oil level.
High Temperature
- In the event of high
temperature, the “high temperature” lamp will glow
red, and the engine will shut down. To reset the
system controller, place the ON/OFF/AUTO switch
in the OFF position. Check for leaves or debris
blocking air inlets and outlets.
High Engine Speed
- The system controller will
shut down the engine in the event that the engine
operating speed exceeds 4080 rpm for 5 seconds.
The “engine over crank” lamp will glow red. To
reset the system controller, place the
ON/OFF/AUTO switch in the OFF position.
Engine Over crank
- The system controller will
engage the starter for 15 seconds. If the engine
does not start, the system controller will allow the
starter to cool down for 15 seconds, then attempt
to start the engine again. This process will repeat
three times. If the engine does not start after the
third attempt, the red “engine over crank” lamp will
glow. To reset the system controller, place the
ON/OFF/AUTO switch in the OFF position.
System Normal-
This lamp indicates everything is
normal. The lamp will glow while the unit is
running, or in automatic mode.
3.1 Control Box Components
Reference 22: GFCI Receptacle
. The GFCI
(ground fault circuit interrupter) duplex receptacle