12
Route the ground wire from the transfer switch to
the generator control panel (Figure 01192). The
ground lead wire shall only be connected to DIN
rail terminal block location #2 (Figure 01197). This
terminal block is colored GREEN and is rated for
lead wires ranging from 22 AWG to 6 AWG. To
install the ground lead wire into the terminal block,
rotate the set screw counterclockwise to open the
funnel (Figure 01198).
Fig. 01197 - Ground Terminal Block
The set screw that opens the funnel is a size M4.
Strip adequate insulation from the GROUND lead
wire and insert the lead wire completely into the
funnel (Figure 01198). Turn the set screw
clockwise to close the funnel. The set screw has a
torque specification of 16 inch-pounds minimum.
Fig. 01198 - Terminal Block
2.9.2 A.C. Battery Charger Connection
The battery charger is configured to plug into the
Ground Fault Circuit Interrupt (GFCI) receptacle.
This receptacle is located on the left side of the
control box (Figure 01199). The GFCI receptacle
is rated for 125 volts A.C. with a current rating of
20 Amps. The GFCI receptacle accepts either
NEMA 5-15P or NEMA 5-20P electrical plugs. A
125 volt, 20-amp circuit breaker, protects the GFCI
receptacle. If the circuit breaker trips, the black
post in the center of the circuit breaker will be
extended. Allow the circuit breaker to cool and
then press the black post back into the circuit
breaker. The circuit breaker is resettable, and is
located adjacent to the GFCI receptacle.
The battery charger electrical requirements are
115 Volts A.C. with a current rating of 0.8 Amps.
For the battery charger to operate, separate power
must be routed from the home to the generator set
by a separate circuit. Protect the wires with
electrical conduit. This separate circuit connects
into the control box at terminal blocks #2, #3, and
#4 (See figure 01192). Terminal block location #2
is designated for the Ground wire. Terminal block
location #3 is designated for the Neutral lead wire.
Terminal #4 is designated for the “hot” lead wire.
Insert the respective lead wires into the funnels
per Figure 01196.
FACTORY INSTALLED
(DO NOT DISTURB)
LOCATION #2
SET SCREW
CUSTOMER INSTALLED
(GROUND WIRE)
SET SCREW
FUNNEL
CUSTOMER INSTALLED
AUTO/OFF/MANUAL
SELECTOR SWITCH