Performing RAID maintenance
Standard 1.0
204
CallPilot
4
Select Physical Device, and then press Enter.
Result:
The Physical Drive Selection window appears. All hard drives
are online
.
5
In the Physical Drive Selection window, select the fourth hard drive, and
then press Enter.
Result:
The device pop-up menu appears.
6
Select Advanced Options, and then press Enter.
Result:
The advanced options pop-up menu appears.
7
Select Make Drive Offline, and then press Enter.
Result:
A message appears warning that making a drive offline may
cause data corruption. For this procedure, disregard this message.
8
Select Yes, and then press Enter.
Result:
The system prompts you to confirm.
9
Select Yes, and then press Enter.
Result:
You return to the Physical Drive Selection window. The hard
drive that was selected is now set to Offline.
.
CAUTION
Risk of lost or corrupted data
All hard drives must be online before you continue with the rest
of this procedure.
.
CAUTION
Risk of data corruption
Ensure that you select a pre-upgrade drive for this step. If this
is a standard configuration and you have followed the
instructions in this procedure, the fourth, fifth, and sixth hard
drives are the pre-upgrade drives. If this is not correct for your
system, contact Nortel Networks technical support.
Содержание CallPilot 1001rp
Страница 2: ...P0949455...
Страница 6: ...vi CallPilot Publication history Standard 1 0...
Страница 38: ...Troubleshooting your CallPilot system Standard 1 0 38 CallPilot...
Страница 62: ...Using Windows NT online diagnostic tools Standard 1 0 62 CallPilot...
Страница 74: ...Using serial port diagnostic tools Standard 1 0 74 CallPilot...
Страница 88: ...Using CallPilot Manager to monitor hardware Standard 1 0 88 CallPilot...
Страница 114: ...Using CallPilot Manager to monitor hardware Standard 1 0 114 CallPilot...
Страница 150: ...Replacing basic chassis components Standard 1 0 150 CallPilot...
Страница 168: ...Replacing a hard drive tape drive CD ROM drive or floppy drive Standard 1 0 168 CallPilot...
Страница 178: ...Performing RAID maintenance Standard 1 0 178 CallPilot...
Страница 260: ...Performing RAID maintenance Standard 1 0 260 CallPilot...
Страница 274: ...Replacing or adding voice processing boards Standard 1 0 274 CallPilot...
Страница 280: ...Replacing the video card Standard 1 0 280 CallPilot...
Страница 292: ...Replacing the network cards Standard 1 0 292 CallPilot...
Страница 320: ...Maintaining the Pentium II SBC card Standard 1 0 320 CallPilot Pentium II SBC...
Страница 326: ...Maintaining the Pentium II SBC card Standard 1 0 326 CallPilot 22 Reconnect the serial port cables EMI gasket...
Страница 348: ...Maintaining the Pentium III SBC card Standard 1 0 348 CallPilot...
Страница 367: ......