PROBLEM

SYMPTOM(S)

POSSIBLE CAUSE

CORRECTIVE ACTION

Apparent controller 

display malfunction

Display Blank

Blown Fuse

Check Fuses

Board Failure

Contact your local distributor for 

further assistance.

Unrealistic temperature 

displayed

Probe loose,off connection 

or defective probe

Inspect probe cable and terminal 

connection Replace probe

Erratic or inaccurate 

temperature readings

Probe not completely in 

thermal well

Inspect probe and check readings 

against independent source (eg. 

temperature analyzer/pyrometer/

ice bath) both in temperature well 

and to ambient

Defective probe

Replace probe

Unrealistic pressure 

displayed

Transducer loose, off 

connection or defective 

transducer

Inspect transducer cable and 

terminal connection
Replace transducer

High pressure drop 

across dryer

Outlet pressure substantially 

lower than inlet pressure 

System operating tempera-

ture is above 32°F

Inlet and outlet valves not 

completely open

Open valves

Inlet and outlet filters 

blocked up

Change filter elements

Outlet pressure substantially 

lower than inlet pressure 

System operating tempera-

ture is below 32°F

Compressor relay / contactor 

stuck.

Replace relay / contactor.

Microprocessor Control relay 

bad

Replace relay

Probe not completely in 

thermal well

Inspect probe and check readings 

against independent source (eg. 

temperature analyzer/pyrometer/

ice bath) both in exchanger well 

and to ambient

Problem persists

Turn dryer off and consult your 

local distributor for further 

assistance

Condensate drain does 

not fire

Inlet / outlet pipe internal 

diameter too small causing 

air-lock or back pressure.

Replace with larger diameter 

piping.

Excessive use of bends / 

elbows in inlet / outlet pipe 

work causing air-lock/ back 

pressure.

Reduce the amount of bends and 

elbows.

Outlet pipe too long / too 

high causing back pressure.

Reconfigure condensate piping.

More than one condensate 

source connected providing 

alternative path for 

condensate.

Reroute condensate to eliminate 

secondary path. Install check 

valves as required.

11.0 TROUBLESHOOTINg

120.26A D4290NCHPW400F Installation Operation and Maintenance Manual

Содержание D4290NCHP

Страница 1: ...na High Pressure Cycling Refrigerated Dryer Models D4290NCHP D5635NCHP AND D7055NCHP Operator s Manual Manual Del Operador ES Manual do Operador PT Manuel De L op rateur FR Operator s Manual EN 120 26...

Страница 2: ...IONS 11 7 6 6 START MODES 12 7 6 6 1 Manual Mode 12 7 6 6 2 Auto Restart Mode 12 7 6 6 3 Remote Automatic Mode 12 contents page 8 0 INSTALLATION AND INITIAL START UP 13 8 1 LOCATION AND MOUNTING 13 8...

Страница 3: ...liable for any repairs replacements or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company s prior written approval The effects of corrosion erosio...

Страница 4: ...ment of company policy as the message relates directly or indirectly to the safety of personnel or protection of property Notice should not be associated directly with a hazard or hazardous situation...

Страница 5: ...ssure Will Cause Injury Death Or Property Damage Relieve Press Before Servicing Condensate Drain Discharges Under Pressure Drain Requires Periodic Cleaning Service READ TECHNICAL MANUAL Removing fuses...

Страница 6: ...high pressure condensate drain installed on the dryer requires the user to supply clean dry air 80 120 psig for proper operation Refer to the instruction label on the condensate drain for details A sm...

Страница 7: ...ingersollrandproducts com PROCESS AND INSTRUMENTIONA DIAGRAM D4290NCHP WATERCOOLED 550130 FIGURE 1 7 0 PRINCIPLES OF OPERATION 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 8: ...ollrandproducts com PROCESS AND INTRUMENTATION DIAGRAM D5635NCHP D7055NCHP AIR AND WATERCOOLED 550116 FIGURE 1 7 0 PRINCIPLES OF OPERATION 120 26A D4290NCHPW400F Installation Operation and Maintenance...

Страница 9: ...ct to provide indication of any of the dryers alarms described later in this manual Contact rated for 2A 120V max The Microprocessor Control features three levels of access The default level CUSTOMER...

Страница 10: ...laying a number of system parameters For NVC dryers Module 1 is supplied with a Deluxe Microprocessor Controller The remaining modules feature a Microprocessor Controller The following summarizes the...

Страница 11: ...AY CHLLR TEMP 36 Press SELECT DISPLAY until CHLLR TEMP is displayed CHLLR TEMP 38 Depress as required to change the CHLLR TEMP to 38 degrees ENTER CHLLR TEMP 38 Pressing ENTER saves the set point SELE...

Страница 12: ...psig FAN 2 OFF 235 psig HPCO Air Cooled 450 psig HPCO Water Cooled 320 psig LPCO 20 psig TABLE 1 7 6 6 START MODES Ingersoll Rand dryers are capable of starting in one of three start modes Note that t...

Страница 13: ...clean dry air 80 psig 120 psig for proper operation Connect clean dry air source to 1 8 NPT port as indicated on condensate drain instruction label Assure needle vent valve is open to allow for displa...

Страница 14: ...VENT NEEDLE VALVE VALVE MUST BE ADJUSTED OPEN TO ALLOW FOR FREE FLOW OF CONDENSATE INTO DRAIN DRAIN WILL NOT FUNCTION IF VALVE IS CLOSED VENT VALVE EXHAUST MUFFLER REMOVE MECHANISM PROTECTIVE SHIPPING...

Страница 15: ...ctory Default No modification required to operate dryer in Manual Mode Once power is applied dryer can be started or stopped by depressing the local ON OFF pushbuttons located on the front panel B Aut...

Страница 16: ...MPERATURE will gradually drop as indicated on the display Once the temperature falls below the HIGH TEMPERATURE ALARM set point the alarm will reset and the LCD panel will return to its default displa...

Страница 17: ...RE PROBE Ts Probe Y N Parameter Display Set Point FAN 1 ON PRESSURE FAN1 OFF See Table 1 FAN 1 OFF PRESSURE FAN1 OFF See Table 1 FAN 2 ON PRESSURE FAN2 ON See Table 1 FAN 2 OFF PRESSURE FAN2 OFF See T...

Страница 18: ...remaining non adjustable parameters may be viewed by depressing the SELECT DISPLAY button as required to arrive at the desired display notice To exit the TECHNICIAN MODE at any time depress the button...

Страница 19: ...or and fan not running Controller indicates compressor is ON Compressor relay may be bad replace relay Check for loose wire connections at contactor or loss of power at control board Defective control...

Страница 20: ...en valves Inlet and outlet filters blocked up Change filter elements Outlet pressure substantially lower than inlet pressure System operating tempera ture is below 32 F Compressor relay contactor stuc...

Страница 21: ...ingersollrandproducts com 21 12 0 WIRING DIAGRAM WIRING DIAGRAM D4290NCHP WATERCOOLED 230 460V 3 60 200 440V 3 50 550126 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 22: ...22 ingersollrandproducts com WIRING DIAGRAM D5635NCHP D7055NCHP WATERCOOLED 230 575V 3 60 200 440V 3 50 550127 12 0 WIRING DIAGRAM 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 23: ...ER TEMP 2 COMPRESSOR ON OFF 3 DRAIN INTERVAL 4 DRAIN ON 5 PERCENT SAVINGS 6 CUMULATIVE DRYER HOURS 7 CUMULATIVE COMPRESSOR HOURS 8 CUSTOMER SET POINTS PUSHBUTTONS 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SEL...

Страница 24: ...COMPRESSOR HOURS 8 CUSTOMER SET POINTS A CHILLER TEMP B DRAIN INTERVAL C DRAIN ON PUSHBUTTONS 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 1 38 1 1 2 MPT WATER OUTLET CUSTOMER CONN 1 1...

Страница 25: ...OL 683724 683724 683724 1 1 1 1 RELAY PUMP 698262 698262 698262 1 RESISTOR CONTROL PANEL DUMMY LOAD 683968 683968 683968 1 TRANSDUCER REFRIGERANT DISCHARGE PRESSURE 682943 682943 682943 1 1 1 1 TRANSD...

Страница 26: ...NO VOLTS PH HZ LBS KG TYPE LB OZ SIZE HP RLA LRA D4290NCHPW 460 3 60 420 380 3 50 2300 1043 R 404 12 0 35 20 2 9 15 7 78 5 D5635NCHPW 460 3 60 420 380 3 50 3800 1721 R 404 11 0 45 27 4 10 5 19 3 105 0...

Страница 27: ...120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 28: ...ingersollrandproducts com 2013 Ingersoll Rand 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Отзывы: