background image

 

ingersollrandproducts.com

7.0 PRINCIPLES OF OPERATION

7.1 INTRODUCTION

Ingersoll Rand

 Nirvana™ Cycling dryers remove moisture 

from compressed air by cooling the air temperature to 

between 36° and 40°F (2 and 4°C). This causes vapors to 

condense into liquid droplets which can then be easily 

removed from the air. The major systems of the dryer which 

contribute to its operation are the Air System, the Moisture 

Removal System, the Refrigeration System, the Thermal 

Mass Circulating System and the Controls. The following 

paragraphs describe each of the systems in greater detail.

7.2 AIR SYSTEM

The air system consists of the dryer components which are 

in contact with the compressed air. Referring to Figure 1 

and following the bold “AIR FLOW,” hot saturated air from 

the compressor enters the precooler/reheater where the air 

temperature is reduced prior to entering the chiller by the 

cool air exiting the air/moisture separator. This precooling 

allows for the use of a smaller refrigeration system. The air 

then goes into the chiller section where it is further cooled 

to the desired dew point by a thermal mass fluid. The 

temperature of the thermal mass fluid is maintained by the 

refrigeration circuit and controls. The air continues to the 

separator where moisture is removed, thereby, allowing the 

cool, dry air to return back to the precooler/reheater to be 

heated by the incoming moist hot air. The air exiting the 

“reheater” portion of the dryer should be approximately 15°- 

20°F lower than the inlet air temperature based on standard 

conditions at full rated flow.

7.3 MOISTURE REMOVAL SYSTEM

Ingersoll Rand

 condensate drains discharge condensed 

moisture and lubricants (condensate) from compressed air 

equipment.  Consistent discharging of condensate from 

compressed air equipment is essential for proper equipment 

operation and performance. The drain valve is designed for 

trouble-free and maintenance free draining of unwanted 

accumulations of condensation and other foreign matter 

from any collection point in a compressed air system without 

the need for electricity.
The high pressure condensate drain installed on the dryer 

requires the user to supply clean dry air (80 - 120 psig) 

for proper operation. Refer to the instruction label on the 

condensate drain for details. A small volume of air must be 

displaced (vented to atmosphere) to allow for the collection 

of condensate. Make certain the vent valve on the drain is 

open to assure proper drain operation.

7.4 REFRIgERATION SYSTEM

The Refrigeration System consists of all the components 

which handle. This is a hermetically sealed closed-loop 

system. Referring to Figure 1 and following the phantom 

“REFRIG FLOW,” refrigerant is shown leaving the evaporator 

section where, in the process of removing heat, it is changed 

from a low pressure liquid into a low pressure gas. This 

gas enters the suction side of the compressor where it is 

compressed into a high pressure gas. The high pressure 

gas is cooled in the air cooled or water cooled condenser 

section until it becomes a high pressure liquid. It then 

goes through a permanent filter dryer that ensures the 

refrigeration system is free of contaminants. A thermostatic 

expansion valve meters the refrigerant for introduction into 

the evaporator. The refrigerant pressure is reduced upon 

entering the evaporator where as it evaporates, heat is 

removed from the thermal mass fluid.

7.5 THERMAL MASS CIRCULATINg SYSTEM

The thermal mass fluid in a 

Ingersoll Rand

 Nirvana™ 

Cycling dryer is continuously circulated in a closed pump 

loop system. Referring to Figure 1 and following the dashed 

“THERMAL MASS FLUID” line, the heat is removed from 

the fluid in the evaporator by the refrigeration system. The 

thermal mass reservoir is sized to minimize refrigeration 

cycles during reduced air load periods. The thermal mass 

fluid is pulled from the bottom of the reservoir and pumped 

through the chiller, removing heat from the air and returned 

to the evaporator. The pump utilized on 

Ingersoll Rand

 

Nirvana™ Cycling dryer is a maintenance-free, quiet cartridge 

circulator pump similar to those used in residential water 

systems. While the refrigeration system cycles on and off 

based on loading conditions, the circulating pump runs 

continuously to maintain flow through the chiller at all times.

120.26A D4290NCHPW400F Installation Operation and Maintenance Manual

Содержание D4290NCHP

Страница 1: ...na High Pressure Cycling Refrigerated Dryer Models D4290NCHP D5635NCHP AND D7055NCHP Operator s Manual Manual Del Operador ES Manual do Operador PT Manuel De L op rateur FR Operator s Manual EN 120 26...

Страница 2: ...IONS 11 7 6 6 START MODES 12 7 6 6 1 Manual Mode 12 7 6 6 2 Auto Restart Mode 12 7 6 6 3 Remote Automatic Mode 12 contents page 8 0 INSTALLATION AND INITIAL START UP 13 8 1 LOCATION AND MOUNTING 13 8...

Страница 3: ...liable for any repairs replacements or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company s prior written approval The effects of corrosion erosio...

Страница 4: ...ment of company policy as the message relates directly or indirectly to the safety of personnel or protection of property Notice should not be associated directly with a hazard or hazardous situation...

Страница 5: ...ssure Will Cause Injury Death Or Property Damage Relieve Press Before Servicing Condensate Drain Discharges Under Pressure Drain Requires Periodic Cleaning Service READ TECHNICAL MANUAL Removing fuses...

Страница 6: ...high pressure condensate drain installed on the dryer requires the user to supply clean dry air 80 120 psig for proper operation Refer to the instruction label on the condensate drain for details A sm...

Страница 7: ...ingersollrandproducts com PROCESS AND INSTRUMENTIONA DIAGRAM D4290NCHP WATERCOOLED 550130 FIGURE 1 7 0 PRINCIPLES OF OPERATION 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 8: ...ollrandproducts com PROCESS AND INTRUMENTATION DIAGRAM D5635NCHP D7055NCHP AIR AND WATERCOOLED 550116 FIGURE 1 7 0 PRINCIPLES OF OPERATION 120 26A D4290NCHPW400F Installation Operation and Maintenance...

Страница 9: ...ct to provide indication of any of the dryers alarms described later in this manual Contact rated for 2A 120V max The Microprocessor Control features three levels of access The default level CUSTOMER...

Страница 10: ...laying a number of system parameters For NVC dryers Module 1 is supplied with a Deluxe Microprocessor Controller The remaining modules feature a Microprocessor Controller The following summarizes the...

Страница 11: ...AY CHLLR TEMP 36 Press SELECT DISPLAY until CHLLR TEMP is displayed CHLLR TEMP 38 Depress as required to change the CHLLR TEMP to 38 degrees ENTER CHLLR TEMP 38 Pressing ENTER saves the set point SELE...

Страница 12: ...psig FAN 2 OFF 235 psig HPCO Air Cooled 450 psig HPCO Water Cooled 320 psig LPCO 20 psig TABLE 1 7 6 6 START MODES Ingersoll Rand dryers are capable of starting in one of three start modes Note that t...

Страница 13: ...clean dry air 80 psig 120 psig for proper operation Connect clean dry air source to 1 8 NPT port as indicated on condensate drain instruction label Assure needle vent valve is open to allow for displa...

Страница 14: ...VENT NEEDLE VALVE VALVE MUST BE ADJUSTED OPEN TO ALLOW FOR FREE FLOW OF CONDENSATE INTO DRAIN DRAIN WILL NOT FUNCTION IF VALVE IS CLOSED VENT VALVE EXHAUST MUFFLER REMOVE MECHANISM PROTECTIVE SHIPPING...

Страница 15: ...ctory Default No modification required to operate dryer in Manual Mode Once power is applied dryer can be started or stopped by depressing the local ON OFF pushbuttons located on the front panel B Aut...

Страница 16: ...MPERATURE will gradually drop as indicated on the display Once the temperature falls below the HIGH TEMPERATURE ALARM set point the alarm will reset and the LCD panel will return to its default displa...

Страница 17: ...RE PROBE Ts Probe Y N Parameter Display Set Point FAN 1 ON PRESSURE FAN1 OFF See Table 1 FAN 1 OFF PRESSURE FAN1 OFF See Table 1 FAN 2 ON PRESSURE FAN2 ON See Table 1 FAN 2 OFF PRESSURE FAN2 OFF See T...

Страница 18: ...remaining non adjustable parameters may be viewed by depressing the SELECT DISPLAY button as required to arrive at the desired display notice To exit the TECHNICIAN MODE at any time depress the button...

Страница 19: ...or and fan not running Controller indicates compressor is ON Compressor relay may be bad replace relay Check for loose wire connections at contactor or loss of power at control board Defective control...

Страница 20: ...en valves Inlet and outlet filters blocked up Change filter elements Outlet pressure substantially lower than inlet pressure System operating tempera ture is below 32 F Compressor relay contactor stuc...

Страница 21: ...ingersollrandproducts com 21 12 0 WIRING DIAGRAM WIRING DIAGRAM D4290NCHP WATERCOOLED 230 460V 3 60 200 440V 3 50 550126 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 22: ...22 ingersollrandproducts com WIRING DIAGRAM D5635NCHP D7055NCHP WATERCOOLED 230 575V 3 60 200 440V 3 50 550127 12 0 WIRING DIAGRAM 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 23: ...ER TEMP 2 COMPRESSOR ON OFF 3 DRAIN INTERVAL 4 DRAIN ON 5 PERCENT SAVINGS 6 CUMULATIVE DRYER HOURS 7 CUMULATIVE COMPRESSOR HOURS 8 CUSTOMER SET POINTS PUSHBUTTONS 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SEL...

Страница 24: ...COMPRESSOR HOURS 8 CUSTOMER SET POINTS A CHILLER TEMP B DRAIN INTERVAL C DRAIN ON PUSHBUTTONS 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 1 38 1 1 2 MPT WATER OUTLET CUSTOMER CONN 1 1...

Страница 25: ...OL 683724 683724 683724 1 1 1 1 RELAY PUMP 698262 698262 698262 1 RESISTOR CONTROL PANEL DUMMY LOAD 683968 683968 683968 1 TRANSDUCER REFRIGERANT DISCHARGE PRESSURE 682943 682943 682943 1 1 1 1 TRANSD...

Страница 26: ...NO VOLTS PH HZ LBS KG TYPE LB OZ SIZE HP RLA LRA D4290NCHPW 460 3 60 420 380 3 50 2300 1043 R 404 12 0 35 20 2 9 15 7 78 5 D5635NCHPW 460 3 60 420 380 3 50 3800 1721 R 404 11 0 45 27 4 10 5 19 3 105 0...

Страница 27: ...120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 28: ...ingersollrandproducts com 2013 Ingersoll Rand 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Отзывы: