background image

ingersollrandproducts.com 

13

8.0 INSTALLATION AND INITIAL START-UP

8.1 LOCATION AND MOUNTINg

The dryer should not be located in an area where ambient 

temperature is likely to exceed 113°F (45°C) or be less 

than 50°F (10°C). The dryer must be located in an area 

that provides sufficient clearance from walls and other 

adjoining equipment to allow easy access for servicing 

and maintenance requirements. A minimum of 18 inches is 

required to allow free flow of air to the condenser inlet.
If loads fluctuate widely, the dryer should be positioned 

ahead of the receiver and sufficient storage capacity 

downstream is necessary to prevent excessive air flow 

through the dryer.
When installed after any compressor that causes significant 

vibration or air pulsation, such as reciprocating compressors, 

proper vibration isolation and pulsation dampening devices 

should be added to protect the dryer.

 NOTICE

Failure to comply to the above instructions may 

result in equipment malfunction and will void 

warranty.

 NOTICE

Always use a backup wrench when making any 

threaded connection to the dryer. Failure to use a 

backup wrench may result in damaged tubing and 

components internal to the cabinet.

8.2 PIPINg AND VALVES

Install piping, fittings and accessories as required for specific 

site conditions and requirements. Figure 3 indicates a typical 

piping arrangement for a refrigerated dryer, including dryer 

and filter bypasses. This figure can be used as a guide for 

valve and accessory placement in the system.
A high-pressure condensate drain is preinstalled at the 

factory.  These drains require the user to provide clean, dry 

air (80 psig - 120 psig) for proper operation.  Connect clean, 

dry air source to 1/8” NPT port as indicated on condensate 

drain instruction label. Assure needle vent valve is open to 

allow for displacement of air with condensate in reservoir.

8.3 FILTRATION

To protect the air dryer from gross contamination associated 

with compressor oil and debris and ensure maximum dryer 

performance, a pre-filter is recommended. Pre-filters and 

post-filters sized to your drying application can be provided 

by 

Ingersoll Rand

 and are available factory installed. Call 

your local distributor to select the filter that best suits 

your filtration requirements. In addition to air filtration, 

condensate discharge oil/water separators are also available 

to address stringent EPA regulations.

8.4 ENVIRONMENTAL CONSIDERATIONS

In many applications, high pressure dryers are a component 

of air systems that use high-pressure, oil-free compressors.  

These compressors can generate condensate that is 

acidic.   Such acidic condensate by itself is not considered 

problematic for the dryer.  However, in environments where 

the air compressor is ingesting certain airborne chemicals, 

such as the off-gassing from a thermal processing or blow 

molding operation, the acidic condensate, when mixed with 

the resulting contaminants, can result in a strong organic 

acid that can be detrimental to the dryer’s internal surfaces.  

This condition is characterized by acidic condensate 

(ph below 5.0), condensate with an acrid odor and / or 

condensate with a distinct yellow color.  Should any of these 

conditions be observed, it is recommended that the air 

source for the air compressor(s) be relocated such that intake 

air for the air compressors is derived from outside the facility.

120.26A D4290NCHPW400F Installation Operation and Maintenance Manual

Содержание D4290NCHP

Страница 1: ...na High Pressure Cycling Refrigerated Dryer Models D4290NCHP D5635NCHP AND D7055NCHP Operator s Manual Manual Del Operador ES Manual do Operador PT Manuel De L op rateur FR Operator s Manual EN 120 26...

Страница 2: ...IONS 11 7 6 6 START MODES 12 7 6 6 1 Manual Mode 12 7 6 6 2 Auto Restart Mode 12 7 6 6 3 Remote Automatic Mode 12 contents page 8 0 INSTALLATION AND INITIAL START UP 13 8 1 LOCATION AND MOUNTING 13 8...

Страница 3: ...liable for any repairs replacements or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company s prior written approval The effects of corrosion erosio...

Страница 4: ...ment of company policy as the message relates directly or indirectly to the safety of personnel or protection of property Notice should not be associated directly with a hazard or hazardous situation...

Страница 5: ...ssure Will Cause Injury Death Or Property Damage Relieve Press Before Servicing Condensate Drain Discharges Under Pressure Drain Requires Periodic Cleaning Service READ TECHNICAL MANUAL Removing fuses...

Страница 6: ...high pressure condensate drain installed on the dryer requires the user to supply clean dry air 80 120 psig for proper operation Refer to the instruction label on the condensate drain for details A sm...

Страница 7: ...ingersollrandproducts com PROCESS AND INSTRUMENTIONA DIAGRAM D4290NCHP WATERCOOLED 550130 FIGURE 1 7 0 PRINCIPLES OF OPERATION 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 8: ...ollrandproducts com PROCESS AND INTRUMENTATION DIAGRAM D5635NCHP D7055NCHP AIR AND WATERCOOLED 550116 FIGURE 1 7 0 PRINCIPLES OF OPERATION 120 26A D4290NCHPW400F Installation Operation and Maintenance...

Страница 9: ...ct to provide indication of any of the dryers alarms described later in this manual Contact rated for 2A 120V max The Microprocessor Control features three levels of access The default level CUSTOMER...

Страница 10: ...laying a number of system parameters For NVC dryers Module 1 is supplied with a Deluxe Microprocessor Controller The remaining modules feature a Microprocessor Controller The following summarizes the...

Страница 11: ...AY CHLLR TEMP 36 Press SELECT DISPLAY until CHLLR TEMP is displayed CHLLR TEMP 38 Depress as required to change the CHLLR TEMP to 38 degrees ENTER CHLLR TEMP 38 Pressing ENTER saves the set point SELE...

Страница 12: ...psig FAN 2 OFF 235 psig HPCO Air Cooled 450 psig HPCO Water Cooled 320 psig LPCO 20 psig TABLE 1 7 6 6 START MODES Ingersoll Rand dryers are capable of starting in one of three start modes Note that t...

Страница 13: ...clean dry air 80 psig 120 psig for proper operation Connect clean dry air source to 1 8 NPT port as indicated on condensate drain instruction label Assure needle vent valve is open to allow for displa...

Страница 14: ...VENT NEEDLE VALVE VALVE MUST BE ADJUSTED OPEN TO ALLOW FOR FREE FLOW OF CONDENSATE INTO DRAIN DRAIN WILL NOT FUNCTION IF VALVE IS CLOSED VENT VALVE EXHAUST MUFFLER REMOVE MECHANISM PROTECTIVE SHIPPING...

Страница 15: ...ctory Default No modification required to operate dryer in Manual Mode Once power is applied dryer can be started or stopped by depressing the local ON OFF pushbuttons located on the front panel B Aut...

Страница 16: ...MPERATURE will gradually drop as indicated on the display Once the temperature falls below the HIGH TEMPERATURE ALARM set point the alarm will reset and the LCD panel will return to its default displa...

Страница 17: ...RE PROBE Ts Probe Y N Parameter Display Set Point FAN 1 ON PRESSURE FAN1 OFF See Table 1 FAN 1 OFF PRESSURE FAN1 OFF See Table 1 FAN 2 ON PRESSURE FAN2 ON See Table 1 FAN 2 OFF PRESSURE FAN2 OFF See T...

Страница 18: ...remaining non adjustable parameters may be viewed by depressing the SELECT DISPLAY button as required to arrive at the desired display notice To exit the TECHNICIAN MODE at any time depress the button...

Страница 19: ...or and fan not running Controller indicates compressor is ON Compressor relay may be bad replace relay Check for loose wire connections at contactor or loss of power at control board Defective control...

Страница 20: ...en valves Inlet and outlet filters blocked up Change filter elements Outlet pressure substantially lower than inlet pressure System operating tempera ture is below 32 F Compressor relay contactor stuc...

Страница 21: ...ingersollrandproducts com 21 12 0 WIRING DIAGRAM WIRING DIAGRAM D4290NCHP WATERCOOLED 230 460V 3 60 200 440V 3 50 550126 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 22: ...22 ingersollrandproducts com WIRING DIAGRAM D5635NCHP D7055NCHP WATERCOOLED 230 575V 3 60 200 440V 3 50 550127 12 0 WIRING DIAGRAM 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 23: ...ER TEMP 2 COMPRESSOR ON OFF 3 DRAIN INTERVAL 4 DRAIN ON 5 PERCENT SAVINGS 6 CUMULATIVE DRYER HOURS 7 CUMULATIVE COMPRESSOR HOURS 8 CUSTOMER SET POINTS PUSHBUTTONS 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SEL...

Страница 24: ...COMPRESSOR HOURS 8 CUSTOMER SET POINTS A CHILLER TEMP B DRAIN INTERVAL C DRAIN ON PUSHBUTTONS 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 1 38 1 1 2 MPT WATER OUTLET CUSTOMER CONN 1 1...

Страница 25: ...OL 683724 683724 683724 1 1 1 1 RELAY PUMP 698262 698262 698262 1 RESISTOR CONTROL PANEL DUMMY LOAD 683968 683968 683968 1 TRANSDUCER REFRIGERANT DISCHARGE PRESSURE 682943 682943 682943 1 1 1 1 TRANSD...

Страница 26: ...NO VOLTS PH HZ LBS KG TYPE LB OZ SIZE HP RLA LRA D4290NCHPW 460 3 60 420 380 3 50 2300 1043 R 404 12 0 35 20 2 9 15 7 78 5 D5635NCHPW 460 3 60 420 380 3 50 3800 1721 R 404 11 0 45 27 4 10 5 19 3 105 0...

Страница 27: ...120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 28: ...ingersollrandproducts com 2013 Ingersoll Rand 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Отзывы: