2.0 INTRODUCTION

The 

Ingersoll Rand

 Nirvana Cycling refrigerated air dryer 

removes moisture, oil vapor, and other contaminants from 

compressed air. These contaminants are detrimental to 

pneumatically operated appliances, controls, instruments, 

machinery and tools. This is accomplished by cooling the air 

with a refrigeration unit to a temperature at which moisture 

in the air is condensed and separated from the airstream. 

The temperature the air is cooled to, normally between 36 

and 40°F, is known as dew point. This dryer can be easily 

installed into various pneumatic systems in which dry air is 

required or desired. Please refer to Principles of Operation 

for complete operating details.

3.0 WARRANTY

The Company warrants that the equipment manufactured 

by it and delivered hereunder will be free of defects in 

material and workmanship for a period of twelve months 

from the date of placing the Equipment in operation or 

eighteen months from the date of shipment from the 

factory, whichever shall first occur. The Purchaser shall be 

obligated to promptly report any failure to conform to 

this warranty, in writing to the Company in said period, 

whereupon the Company shall, at its option, correct such 

nonconformity, by suitable repair to such equipment 

or, furnish a replacement part F.O.B. point of shipment, 

provided the Purchaser has stored, installed, maintained and 

operated such Equipment in accordance with good industry 

practices and has complied with specific recommendations 

of the Company. Accessories or equipment furnished by 

the Company, but manufactured by others, shall carry 

whatever warranty the manufacturers have conveyed to the 

Company and which can be passed on to the Purchaser. The 

Company shall not be liable for any repairs, replacements, 

or adjustments to the Equipment or any costs of labor 

performed by the Purchaser or others without Company’s 

prior written approval.
The effects of corrosion, erosion and normal wear and tear 

are specifically excluded. Performance warranties are limited 

to those specifically stated within the Company’s proposal. 

Unless responsibility for meeting such performance 

warranties are limited to specified tests, the Company’s 

obligation shall be to correct in the manner and for the 

period of time provided above.

THE COMPANY MAKES NO OTHER WARRANTY OR 

REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED 

OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED 

WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A 

PARTICULAR PURPOSE, ARE HERBY DISCLAIMED.
Correction by the Company of nonconformities whether 

patent or latent, in the manner and for the period of time 

provided above, shall constitute fulfillment of all liabilities of 

the Company for such nonconformities whether based on 

contract, warranty negligence, indemnity, strict liability or 

otherwise with respect to or arising out of such Equipment.
The Purchaser shall not operate Equipment which is 

considered to be defective, without first notifying the 

Company in writing of its intention to do so. Any such use of 

Equipment will be at Purchaser’s sole risk and liability.
Note that this is 

Ingersoll Rand

 standard warranty. Any 

warranty in force at the time of purchase of the equipment 

or negotiated as part of the purchase order may take prec-

edence over this warranty.

4.0 REFRIgERATED DRYER NOMENCLATURE

DRYER NOMINAL*

FLOW 

(Nm³/hr)

NIRVANA

CYCLINg

HIgH 

PRESSURE

CONDENSER

TYPE

POWER

RATINg

D

4290

5635

7055

NC

HP

A = AIR

W = WATER

4 = 460-3-60  

6 = 575-3-60 

7 = 380-3-50    

0 = NEMA 1

H = NEMA 4

* Nominal Flows indicated are for 100°F inlet temperature, 100°F ambient temperature and 580 psig compressed air pressure

120.26A D4290NCHPW400F Installation Operation and Maintenance Manual

Содержание D4290NCHP

Страница 1: ...na High Pressure Cycling Refrigerated Dryer Models D4290NCHP D5635NCHP AND D7055NCHP Operator s Manual Manual Del Operador ES Manual do Operador PT Manuel De L op rateur FR Operator s Manual EN 120 26...

Страница 2: ...IONS 11 7 6 6 START MODES 12 7 6 6 1 Manual Mode 12 7 6 6 2 Auto Restart Mode 12 7 6 6 3 Remote Automatic Mode 12 contents page 8 0 INSTALLATION AND INITIAL START UP 13 8 1 LOCATION AND MOUNTING 13 8...

Страница 3: ...liable for any repairs replacements or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company s prior written approval The effects of corrosion erosio...

Страница 4: ...ment of company policy as the message relates directly or indirectly to the safety of personnel or protection of property Notice should not be associated directly with a hazard or hazardous situation...

Страница 5: ...ssure Will Cause Injury Death Or Property Damage Relieve Press Before Servicing Condensate Drain Discharges Under Pressure Drain Requires Periodic Cleaning Service READ TECHNICAL MANUAL Removing fuses...

Страница 6: ...high pressure condensate drain installed on the dryer requires the user to supply clean dry air 80 120 psig for proper operation Refer to the instruction label on the condensate drain for details A sm...

Страница 7: ...ingersollrandproducts com PROCESS AND INSTRUMENTIONA DIAGRAM D4290NCHP WATERCOOLED 550130 FIGURE 1 7 0 PRINCIPLES OF OPERATION 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 8: ...ollrandproducts com PROCESS AND INTRUMENTATION DIAGRAM D5635NCHP D7055NCHP AIR AND WATERCOOLED 550116 FIGURE 1 7 0 PRINCIPLES OF OPERATION 120 26A D4290NCHPW400F Installation Operation and Maintenance...

Страница 9: ...ct to provide indication of any of the dryers alarms described later in this manual Contact rated for 2A 120V max The Microprocessor Control features three levels of access The default level CUSTOMER...

Страница 10: ...laying a number of system parameters For NVC dryers Module 1 is supplied with a Deluxe Microprocessor Controller The remaining modules feature a Microprocessor Controller The following summarizes the...

Страница 11: ...AY CHLLR TEMP 36 Press SELECT DISPLAY until CHLLR TEMP is displayed CHLLR TEMP 38 Depress as required to change the CHLLR TEMP to 38 degrees ENTER CHLLR TEMP 38 Pressing ENTER saves the set point SELE...

Страница 12: ...psig FAN 2 OFF 235 psig HPCO Air Cooled 450 psig HPCO Water Cooled 320 psig LPCO 20 psig TABLE 1 7 6 6 START MODES Ingersoll Rand dryers are capable of starting in one of three start modes Note that t...

Страница 13: ...clean dry air 80 psig 120 psig for proper operation Connect clean dry air source to 1 8 NPT port as indicated on condensate drain instruction label Assure needle vent valve is open to allow for displa...

Страница 14: ...VENT NEEDLE VALVE VALVE MUST BE ADJUSTED OPEN TO ALLOW FOR FREE FLOW OF CONDENSATE INTO DRAIN DRAIN WILL NOT FUNCTION IF VALVE IS CLOSED VENT VALVE EXHAUST MUFFLER REMOVE MECHANISM PROTECTIVE SHIPPING...

Страница 15: ...ctory Default No modification required to operate dryer in Manual Mode Once power is applied dryer can be started or stopped by depressing the local ON OFF pushbuttons located on the front panel B Aut...

Страница 16: ...MPERATURE will gradually drop as indicated on the display Once the temperature falls below the HIGH TEMPERATURE ALARM set point the alarm will reset and the LCD panel will return to its default displa...

Страница 17: ...RE PROBE Ts Probe Y N Parameter Display Set Point FAN 1 ON PRESSURE FAN1 OFF See Table 1 FAN 1 OFF PRESSURE FAN1 OFF See Table 1 FAN 2 ON PRESSURE FAN2 ON See Table 1 FAN 2 OFF PRESSURE FAN2 OFF See T...

Страница 18: ...remaining non adjustable parameters may be viewed by depressing the SELECT DISPLAY button as required to arrive at the desired display notice To exit the TECHNICIAN MODE at any time depress the button...

Страница 19: ...or and fan not running Controller indicates compressor is ON Compressor relay may be bad replace relay Check for loose wire connections at contactor or loss of power at control board Defective control...

Страница 20: ...en valves Inlet and outlet filters blocked up Change filter elements Outlet pressure substantially lower than inlet pressure System operating tempera ture is below 32 F Compressor relay contactor stuc...

Страница 21: ...ingersollrandproducts com 21 12 0 WIRING DIAGRAM WIRING DIAGRAM D4290NCHP WATERCOOLED 230 460V 3 60 200 440V 3 50 550126 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 22: ...22 ingersollrandproducts com WIRING DIAGRAM D5635NCHP D7055NCHP WATERCOOLED 230 575V 3 60 200 440V 3 50 550127 12 0 WIRING DIAGRAM 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 23: ...ER TEMP 2 COMPRESSOR ON OFF 3 DRAIN INTERVAL 4 DRAIN ON 5 PERCENT SAVINGS 6 CUMULATIVE DRYER HOURS 7 CUMULATIVE COMPRESSOR HOURS 8 CUSTOMER SET POINTS PUSHBUTTONS 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SEL...

Страница 24: ...COMPRESSOR HOURS 8 CUSTOMER SET POINTS A CHILLER TEMP B DRAIN INTERVAL C DRAIN ON PUSHBUTTONS 1 ON 2 OFF 3 RESET 4 TEST 5 SET 6 SELECT DISPLAY 7 ENTER 8 1 38 1 1 2 MPT WATER OUTLET CUSTOMER CONN 1 1...

Страница 25: ...OL 683724 683724 683724 1 1 1 1 RELAY PUMP 698262 698262 698262 1 RESISTOR CONTROL PANEL DUMMY LOAD 683968 683968 683968 1 TRANSDUCER REFRIGERANT DISCHARGE PRESSURE 682943 682943 682943 1 1 1 1 TRANSD...

Страница 26: ...NO VOLTS PH HZ LBS KG TYPE LB OZ SIZE HP RLA LRA D4290NCHPW 460 3 60 420 380 3 50 2300 1043 R 404 12 0 35 20 2 9 15 7 78 5 D5635NCHPW 460 3 60 420 380 3 50 3800 1721 R 404 11 0 45 27 4 10 5 19 3 105 0...

Страница 27: ...120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Страница 28: ...ingersollrandproducts com 2013 Ingersoll Rand 120 26A D4290NCHPW400F Installation Operation and Maintenance Manual...

Отзывы: