NE200&300 Quick Start Guide
65
Code
Description
Setting range
Default
Modify
Modbus
Address
FF.10 Reserved
Reserved
Reserved
-
100AH
FF.11
Software
version
number of
control board
1.00~10.00
1
-
100BH
FF.12
Non-standard
version
number of
software
0~255
0
-
100CH
FF.13
②
Heat sink
temperature
-30.0
~
120.0°C
0.0°C
-
100DH
③
IGBT
temperature
0.0
~
140.0°C
0.0°C
-
100DH
FF.14
②
Flux
current
-200.0~200.0%
*
100EH
FF.15
③
Torque
current
-200.0~200.0%
*
100FH
FF.17
Accumulated
kilowatt-hours
(
Upper 16
bits
)
0~65535kWH
0kWH
-
1011H
FF.18
Accumulated
kilowatt-hours
(
Low 16
bits
)
0~65535kWH
0kWH
-
1012H
Group FP Protection Parameters
Code
Description
Setting range
Default Modify
Modbus
Address
FP.00
User
password
0~9999
0: No password
0
○
-
Others: password
protection
FP.01
Parameter
write-in
protection
0: All parameters are
allowed modifying
0
○
--
1: Only FP.01 and FP.03
can be modified