NE200&300 Quick Start Guide
52
Code
Description
Setting range
Default
Modify
Modbus
Address
F8.16
PID output
positive limit
②
0.0~320.0Hz
③
0.0
~
600.0Hz
50.00Hz
○
0910H
F8.17
PID output
negative limit
0.00
~
550.0Hz
0.00Hz
○
0911H
F8.18 PID preset freq.
0.00
~
550.0Hz
0.00Hz
×
0912H
F8.19
Hold time of PID
preset frequency
0.0
~
3600s
0.0s
×
0913H
F8.20
Enable
dormancy
0: Disabled
1: Enabled
0
×
0914H
F8.21 Dormancy delay
0
~
999s
120s
○
0915H
F8.22
Dormancy
threshold
0.0
~
320.0Hz
20.0Hz
○
0916H
F8.23
Awaken
threshold
0.0~100.0%
(relative to pre-set
value)
80.00%
○
0917H
F8.24
PID feedback
offline detection
range
0.0~100.0%
(relative to feedback
measuring range,
0.0% no detection)
0.0%
○
0918H
F8.25
PID feedback
offline detection
time
0.0~50.0s
2.0s
○
0919H
F8.26
PID feedback
offline detection
Min. Freq.
0.00~50.00Hz
10.00Hz
○
091AH
Group F9: Multi-step speed and PLC
Code
Description
Setting range
Default
Mod
ify
Modbus
Addres
s
F9.00 Multi-step freq.1
0.00
~
Max frequency
5.00 Hz
○
0A00H
F9.01 Multi-step freq.2
0.00
~
Max frequency
10.00 Hz
○
0A01H
F9.02 Multi-step freq.3
0.00
~
Max frequency
15.00 Hz
○
0A02H
F9.03 Multi-step freq.4
0.00
~
Max frequency
20.00 Hz
○
0A03H