NE200&300 Quick Start Guide
47
Code
Description
Setting range
Default
Modify
Modbus
Address
③
Frequency
detection value
2 (FDT2 level)
0.00
~
320.0Hz
25.00Hz
○
0808H
F7.09
Freq. detection
lag2 (FDT2-lag)
0.00
~
10.00Hz
1.00Hz
○
0809H
F7.10
Up detection
frequency
0.00
~
550.0Hz
50.00Hz
○
080AH
F7.11
Down detection
frequency
0.00
~
550.0Hz
0.00Hz
○
080BH
F7.12
Torque
detection
reference
0.0
~
200.0%
100.00%
○
080CH
F7.13
Preset Counting
arrival value
0
~
9999
0
○
080DH
F7.14
Preset Timing
arrival value
0.0
~
6553.0s
0.0s
○
080EH
F7.16
AI1 compare
threshold 1
0.00
~
10.00v
0.00v
○
0810H
F7.17
AI1 compare
threshold 2
0.00
~
10.00v
0.00v
○
0811H
F7.18
Analog compare
hysteresis error
0.00
~
30.00v
0.20v
○
0812H
F7.19
②
AO function
definition
③
AO1 output
selection
0: NULL
1: Running freq.
(0~max frequency)
2: Setting freq.
(0~max frequency)
3: Output
current(0
~
2 times
of drive rated
current)
1
○
0813H
F7.20
②
Reserve
Reserve
Reserve
0814H
③
AO2 output
selection
0
○
0814H