NE200&300 Quick Start Guide
36
Code
Description
Setting range
Default
Modify
Modbus
Address
3: 1.2 power decreasing
torque
4: Multiple dots V/F
F4.01 V/F freq. F1
0.0
~
F4.03
10.00Hz
×
0501H
F4.02
V/F voltage
V1
0.0
~
100.0%
20.00%
×
0502H
F4.03 V/F freq. F2
F4.01
~
F4.05
25.00Hz
×
0503H
F4.04
V/F voltage
V2
0.0
~
100.0%
50.00%
×
0504H
F4.05 V/F freq. F3
F4.03
~
F0.10
40.00Hz
×
0505H
F4.06
V/F voltage
V3
0
~
100.0%
80.00%
×
0506H
F4.07 Torque boost
0.0%: Auto boost
0.00%
○
0507H
0.1
~
30.0%: Manual
boost
F4.08
Manual
torque boost
cutoff point
0.00
~
60.00Hz
50.00Hz
○
0508H
F4.09
Slip
compensation
coefficient
0.0
~
200.0%
0.00%
○
0509H
F4.10
Slip
compensation
filtering time
0.01
~
2.55s
0.20s
○
050AH
F4.11
V/F
separation
control
voltage
source
0: disabled
1: Digital setting (F4.12)
2: AI1
3: AI2
4: Pulse
5: communication
0
×
050BH
F4.12
V/F
separation
voltage digital
setting
0V
~
max output voltage
38
0V
○
050CH
F4.13 V/F
0.0s
~
1000.0s
0.0s
○
050DH