NE200&300 Quick Start Guide
30
Code
Description
Setting range
Default
Modify
Modbus
Address
Energy-saving
control select
1: Enable
F2.17 AVR Function
0: Disabled 1: Enabled
2
×
0311H
2: Disabled only at
speed-down
F2.18 Over modulation 0: Enabled 1: Disabled
1
×
0312H
F2.19
③
Droop control 0.00~10.00Hz
0.00Hz
○
0313H
F2.20 Fan control mode
0: Auto mode
1: Always Running
0
×
0314H
F2.21
Instant-power-fail
ure treatment
0: Disabled
②
1: Drop frequency
(Reserved)
0
○
0315H
③
1: Drop frequency
2: Stop directly
F2.22
Instant-power-fail
ure freq. drop
point
210
~
600V
380V:420V
○
0316H
220V:230V
F2.23
Instant-power
failure freq. drop
rate
1-800
400
○
0317H
F2.24
Motor speed
display ratio
0.00
~
500.0%
100.00%
○
0318H
F2.25
UP/DOWN drop
to minus
frequency
0: Enabled
1
○
0319H
1: Disable
F2.26
ENTER key
function
0: No special action
0
○
031AH
1: FWD/REV switching
2: RUN for forward;
Enter for reverse; STOP
for stop
3: Jog
running
F2.27 Freq. resolution 0: 0.01Hz 1: 0.1Hz
0
×
031BH
F2.28
Acc./Dec. time
unit
0: 0.1s 1: 0.01s
1
②
0
③
×
031CH