NE200&300 Quick Start Guide
57
Code
Description
Setting range
Default
Modify
Modbus
Address
FC.08
Input phase loss
detection
1
~
100%
(100% correspond
to 800V)
20%
×
0D08H
FC.09
Input phase loss
detection delay
time
2
~
255s
10s
×
0D09H
FC.10
Output phase loss
detection
0:
Invalid
1: Valid
1
○
0D0AH
FC.11
Terminal close
fault detection
0:
Invalid
1: Valid
1
○
0D0BH
FC.12
Fault auto reset
times
0
~
10,“0” means
auto reset is
disabled. Only 3
faults have auto
reset function
0
×
0D0CH
FC.13
Fault auto reset
interval
0.1
~
20.0s/time
5.0s
×
0D0DH
FC.14
Under-voltage
fault treatment
0: No treatment
1: Auto reset at
power recovery
2: Auto run at power
recovery (Auto run
time interval is
F1.16)
0
○
0D0EH
FC.15 Fast current limit
50.0%~100.0%
(100% means this
function is disabled.)
Depends
on
model
○
0D0FH
FC.16
Fast current limit
time
0.01~1.00s
0.10s
○
0D10H
FC.17
Overvoltage
suppression freq.
0.00~10.00Hz
0.00Hz
○
0D11H
FC.18
Select
suppression
overvoltage
methods
0: method 1
1: method 2
2: method 3
0
○
0D12H