Frequently asked questions

Frequently asked questions

What do you have to think about to get to 

the web site from the Internet?

In most cases where on has a fixed connection to the 
Internet there is some kind of firewall to protect the net-
work. To access a unit inside a firewall, it must be configu-
red to let desired traffic through. To gain access to the web 
site in the RCU from the Internet, port 80 (HTTP/web) must 
open in the firewall and be guided to the RCU unit on the 
inside.

How do I connect an RCU with a cable direc-

tly to a computer, without connecting it to a 

network?

Ethernet networks can have two types of cable: straight-
through or crossover. A straight-through cable is used bet-
ween the computer <-> network equipment. A crossover 
cable is used between a computer <-> another computer 
or for network equipment <-> network equipment. The 
RCU is counted as a computer and shall therefore have a 
crossover cable if it is connected directly to another com-
puter.

Can the RCU become infected with a virus?

No. Visuses are generally always written to infect compu-
ters that run Microsoft Windows, or occasionally Linux. A 
virus is written for a particular operating system or proces-
sor and can only infect the type of platform for which it is 
written. An RCU does not have the same type of proces-
sor as an everyday computer, nor can it therefore become 
infected.

What does ”JAVA support in a browser” 

mean?

To be able to run a program written in JAVA on a compu-
ter, it must have a JVM (Java Virtual Machine) installed. A 
JAVA applet on a web site requires that the browser can 
use this JVM to be able to run the applet. Most current 
browsers can manage this but there is not always a JVM 
installed in the computer. In these cases a JVM must be 
downloaded and installed for everything to work. JVMs 
for many different operating systems can be downloaded 
from: www.java.com. There is also a version on the supp-
lied CD.

What kind of subscription do I need for my 

GSM modem?

If the telephonic data connection to the modem function is 
to be used, a special subscription is required. Refer to the 
“Web interface – Settings” section > “Modem”.
There is no special GSM subscription requirement for the 
other functions. A cash card, normal subscription or a spe-
cial telematics subscription work well. However a cash card 
must be regularly refilled to ensure continued use.

Can I surf to the product via the  

GSM modem?

Yes, it is possible to call in to an RCU if you have a modem 
connected to a computer and have configured the RCU to 

accept this. Via this connection it is then possible to look at 
the web pages and download log files.
However for this function the GSM subscription must inclu-
de a special service for telephonic data connection. Refer 
to the “Web interface – Settings” section > “Modem”.

Can I fetch log files via the GSM modem? How 

do I do it?

Yes, it is possible to call in to an RCU if you have a modem 
connected to a computer and have configured the RCU to 
accept this.
However for this function the GSM subscription must inclu-
de a special service for telephonic data connection. Refer 
to the “Web interface – Settings” section > “Modem”.
Enter the address to the RCU in the browser, and add /cgi-
bin/log.csv. A log-in window will be displayed and then you 
will be asked if you want to open or save the file.

Two log-in windows are displayed, why?

Unfortunately web browsers are often not perfectly inte-
grated with the JVM that is installed in the computer. In 
practice the JVM (that runs the JAVA applets) does not 
understand that the browser has already put up a log-in 
window, and therefore puts up another one when a JAVA 
applet is to be run, for safety’s sake. This will hopefully be 
solved in future versions of browsers and JVMs.

I don’t get a reply when I send an SMS com-

mand to the RCU, what’s wrong?

Probably the telephone number is not registered in the 
RCU, which is necessary to be able to send commands to 
it. Another problem can be that there is no GSM coverage 
where the RCU is located.

What does ”Network mask” mean?

An IP address is composed of 32 bits and the network 
mask defines how many bits are used for the network 
address. The remaining bits identify the computer on the 
network. The net mask looks the same as an IP address, 
e.g. 255.255.0.0 or 255.255.255.0. 

What is a ”default Gateway”?

So that computers that are on separate networks (different 
sub-networks) are able to communicate with each other, 
routers are needed between the networks to “bridge” the 
traffic. Default gateway is the name of the router that is to 
be used to reach the computers that are not on the local 
network. This router then sends the information on to the 
destination or the nearest router that it knows about. 

Which browsers work together with an RCU?

The web pages are optimised for Internet Explorer and 
Mozilla Firefox. Other browsers should work well, but the 
pages may look different.

What is the format of the log files?

The log files in the RCU are of CSV type. This is a usual 
format for log files and is supported by such programs as 
Microsoft Excel.

Содержание RCU 11

Страница 1: ...MOS GB 0825 1 RCU 11 031187 Installation and Maintenance Instructions RCU 11 For FIGHTER 360P 11XX 12XX 1250 13XX...

Страница 2: ......

Страница 3: ...rating data_ ___________________________________ 22 Operating data extended_ __________________________ 23 Alarm status______________________________________ 24 Log ___________________________________...

Страница 4: ...ineers MAC ID Date __________ Signature __________________________________ This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or...

Страница 5: ...arm or freezing protection Note that all configuration of the unit requires that a com puter with support for JAVA applets is connected even if only text messaging is going to be used The RCU enables...

Страница 6: ...ard Crossover network cable Insert a SIM card if the GSM modem is to be used Remember that the pin code must be deactivated and if it is pay as you go that there are credits on the card Connect the RC...

Страница 7: ...ash and Link must light orange 100Mbps or green 10Mbps if the network cable is connected Turn on the computer and insert the CD supplied and follow the instructions Start the configuration program Net...

Страница 8: ...vate in menu 9 1 3 Fighter 11XX Activate in menu 9 2 15 Fighter 12XX Fighter 13XX Activate in menu 9 1 3 11 12 14 13 Start the web browser and enter the RCUs IP address in the address field and press...

Страница 9: ...DHCP is selected in the RCU If the DHCP is not to be used close the DHCP with Netbiter Continue with network settings for the RCU No page is shown when entering the RCU IP address in the web browser S...

Страница 10: ...ute the communication cable 105 down to the area at the bottom of the heat pump Use the supplied connector to connect the commu nication cable from the RCU The CPU card in FIGHTER 360P must have versi...

Страница 11: ...modular cable between the CPU card 34 and the communication card 3 If one or more slaves are connected the remaining modular cable to the com munication card 3 must be connected to the socket oppo sit...

Страница 12: ...commended For connection direct to a compu ter with Internet connection two network cards are requi red in the computer and it must run continuously in order to provide the RCU access to the Internet...

Страница 13: ...n be done in a mobile telephone or by the ser vice provider For a telephonic data connection to the RCU the SIM card needs to have a special telephone number for computer communication Refer to the se...

Страница 14: ...red During startup Not lit No contact with network Steady green 10 Mbit s link Steady orange 100 Mbit s link Not lit Waiting Flashing green TX serial channel serial package receive Flashing red RX ser...

Страница 15: ...rd disk space Windows 95 98 ME NT 2000 XP Network card Ethernet If a different operating system than Windows is used the configuration software can not be used Then connect to the RCU s preset IP addr...

Страница 16: ...he new set tings can be entered To obtain the necessary information concerning your net work settings please contact your network administrator IP Address IP address for the RCU Subnet mask Network ma...

Страница 17: ...irst time enter admin into both entry fields Another log in dia log can be shown depending on the Java version installed The password will be changed later and new users can be added refer to the Web...

Страница 18: ...also a version on the supplied CD The side menu provides navigation in the RCU s internal web pages The side menu has differences depending on which product is used together with the RCU Overview diag...

Страница 19: ...og file change at restart of the RCU or when the log in settings are changed Log In Settings Log are entered the desired paramet ers logging interval and type of log in The selected parameters and log...

Страница 20: ...service personnel E mail Here the settings for handling E mail can be made This is necessary for enabling the RCU to send alarms via E mail to selected users E mail Activates E mail function SMTP serv...

Страница 21: ...formation can be edited by clicking on the names User ID This ID is used when logging on to the RCU via a browser Name User s name E mail The user s E mail address to which alarms are to be sent Mobil...

Страница 22: ...eturn temperature Menu 2 6 C Temperature compressor sensor Menu 1 1 D Temperature hot water sensor Menu 1 0 E Evaporation temperature Menu 5 0 F Extract air temperature Menu 5 1 G Exhaust air temperat...

Страница 23: ...After a few seconds the change is confirmed by FIGHTER 360P and the relevant value is updated The change in value presumes that the user has logged in with writing or administration authority Operati...

Страница 24: ...pro gram for further processing Alarm status This form shows the common alarms that the heat pump has indicated External alarm inputs DI1 and DI2 are not concerned with the heat pump functions but ar...

Страница 25: ...o Electric Boiler XHW 0 3 6 12 24 Extra hot water function Vent 0 1 N 2 Fan speed Off Speed 1 Normal Speed 2 DI 1 2 12 RCU digital inputs STATUS2 Vent nn n Extract air temperature Exh nn n Exhaust air...

Страница 26: ...n C Operational information Here the status is shown of the functions that are ac tivated in the heat pump Overview diagram This is the first page to be displayed after logging in It shows an overview...

Страница 27: ...1 0 Note that the selected RCU offset heating curve is added to the heat pump s internal offset heating curve To change a value click on arrow down and select a va lue from the scrolling list confirm...

Страница 28: ...hat the user has logged in with writing or administration authority Operating data external units In this form the external unit parameters can be changed by clicking on arrow down and selecting a val...

Страница 29: ...terface FIGHTER 1250 A Communication indications Green lamp indicates functioning communications Red lamp indicates communication error B Operating indications Lit lamp indicates an active function C...

Страница 30: ...ffset heating curve is added to the heat pump s internal offset heating curve To change a value click on arrow down and select a va lue from the scrolling list confirm with Set After a few seconds the...

Страница 31: ...In this form the heat regulation parameters can be chan ged by clicking on arrow down and selecting a value from the scrolling list confirming thereafter with Set The change in value presumes that the...

Страница 32: ...his form the external unit parameters can be changed by clicking on arrow down and selecting a value from the scrolling list confirming thereafter with Set The change in value presumes that the user h...

Страница 33: ...ata extended Log Here the log files that are in the RCU can be fetched The parameter log contains selected logged values see the Web interface Settings Log section The alarm log contains all the alarm...

Страница 34: ...Brine out temperature HW On Off Hot water production activated Mode W SA S A Add heat ONLY FIGHTER 11XX 12XX Operating mode Winter Spring Autumn Summer Auto Additional Only S A Add heat ONLY FIGHTER...

Страница 35: ...red marker indicates which unit is being shown Slave is only shown when several heat pumps are connected to the Master B Operating indications Shows operating conditions for installed units Green back...

Страница 36: ...that the selected RCU offset heating curve is added to the heat pump s internal offset heating curve To change a value click on arrow down and select a va lue from the scrolling list confirm with Set...

Страница 37: ...e changed by clicking on arrow down and selecting a value from the scrolling list confirming thereafter with Set The change in value presumes that the user has logged in with writing or administration...

Страница 38: ...witch between different heat pumps in the system by using the scroll list at the top left The change in value presumes that the user has logged in with writing or administration authority Log Here the...

Страница 39: ...ected C F nn n Calculated flow DM nn n Current degree minutes Mode W SA S A Add heat Operating mode Winter Spring Autumn Summer Auto Additional Only XHW 0 3 6 12 24 Extra hot water function A heat On...

Страница 40: ...ications module with GSM modem 3 Antenna 4 Communication port to FIGHTER 5 Network connections 6 Eject button and holder for SIM card 7 Connection of external contact function 8 Label with MAC ID RCU...

Страница 41: ...emperature range 0 60 C CE certification In accordance with EN 50 081 2 1993 and EN 61 000 6 2 1999 Miscellaneous Miscellaneous Enclosed kit L E K LEK LEK LEK LEK LEK Network cable cross over for conn...

Страница 42: ...sible to call in to an RCU if you have a modem connected to a computer and have configured the RCU to accept this Via this connection it is then possible to look at the web pages and download log file...

Страница 43: ......

Страница 44: ...LLEMSTAD NB Tel 0168 477722 Fax 0168 476998 E mail info nibenl nl www nibenl nl V lund Varmeteknik Filial af NIBE AB Brog rdsvej 7 6920 Videb k Tel 97 17 20 33 Fax 97 17 29 33 E mail info volundvt dk...

Отзывы: