19

RCU 11

Web interface – Settings

Modem

Here all the settings that affect the GSM modem can be 
made.

SMS settings

If ”SMS Alarm” is activated, the RCU will send a text mes-
sage (SMS) to all alarm recipients as soon as an alarm is 
activated by the heat pump.
To enable SMS commands to be sent to the RCU, 
“SMS Command” must be set to “On”.
If “Number check of incoming SMS” is set to “Off” the 
SMS command “?STATUS” is accepted from all telephone 
numbers (e.g. for demonstration). Note that other SMS 
commands always require that the number has been recor-
ded on a user.

PPP-server inställningar

A PPP server is used to permit incoming connections to the 
RCU via the modem. This requires that the GSM subscrip-
tion includes a service where a special telephone number 
for computer communication is provided. It is this computer 
number that will then be used during a called computer 
connection to the modem. Contact your GSM operator to 
see if this service will be possible.
The connection can be used to look at web sites or to fetch 
a log file from the RCU. State the user name/password that 
are to be used on logging in, and which IP address shall 
be sent out to the person connecting. This IP number shall 
be in the same sub-network as occupied by the RCU, and 
the IP number must be free. If, for example, the RCU has 
193.12.34.21, the issued IP number must be 193.12.34.X, 
where X is between 1 and 254.

Users

Here takes place handling of users who shall have the right 
to log in to the RCU. Click on  “Add” to add a new user. 
Existing user information can be edited by clicking on the 
names.

User ID: This ID is used when logging on to the RCU 

• 

via a browser.
Name: User’s name.

• 

 E-mail: The user’s E-mail address to which alarms are 

• 

to be sent.
 Mobile: The mobile telephone number that is appro-

• 

ved for incoming SMS commands and to which alarms 
are to be sent.
Alarm receiver: Here is defined which types of alarm 

• 

the user is to receive. Several boxes can be marked.

 

Prio 1: High priority alarm.

 

Prio 2: Low priority alarms.

 

Digital inputs: Alarms from digital inputs.

 

 Heat pump status changed: Alarm if contact bet-
ween RCU and the heat pump is interrupted or 
the heat pump has no power supply.

User level: 

• 
 

 Read: The user may only look at the web site and 
cannot change anything (Control via SMS not per-
mitted).

 

 Write: The user may look at the web site and 
change parameters on the operations pages.

 

 Admin: The user may look at the web site and has 
full authority to change configuration and para-
meters.

 Password: This password is used when logging on to 

• 

the RCU via a browser. The password is to be repeated 
for verification.
Send a test mail: Trial send an e-mail. Settings must be 

• 

made under the ”E-mail” menu first. 
Send a test SMS: Sends an SMS. Settings under the 

• 

”Modem” menu for SMS alarm must be on. If connec-
tion is by the GSM modem the SMS will be sent when 
the connection is disconnected.

The password is case-sensitive and only A-Z, 

a-z and 0-9 are permitted to be used in the 

user ID and password, which means that 

the symbol characters cannot be used.

NOTE!

When connecting via GSM to the RCU it 

does not respond to text messages while 

the conversation is underway but an SMS 

response arrives immediately afterwards.

NOTE!

ModbusTCP

Contact NIBE for current register table.

Содержание RCU 11

Страница 1: ...MOS GB 0825 1 RCU 11 031187 Installation and Maintenance Instructions RCU 11 For FIGHTER 360P 11XX 12XX 1250 13XX...

Страница 2: ......

Страница 3: ...rating data_ ___________________________________ 22 Operating data extended_ __________________________ 23 Alarm status______________________________________ 24 Log ___________________________________...

Страница 4: ...ineers MAC ID Date __________ Signature __________________________________ This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or...

Страница 5: ...arm or freezing protection Note that all configuration of the unit requires that a com puter with support for JAVA applets is connected even if only text messaging is going to be used The RCU enables...

Страница 6: ...ard Crossover network cable Insert a SIM card if the GSM modem is to be used Remember that the pin code must be deactivated and if it is pay as you go that there are credits on the card Connect the RC...

Страница 7: ...ash and Link must light orange 100Mbps or green 10Mbps if the network cable is connected Turn on the computer and insert the CD supplied and follow the instructions Start the configuration program Net...

Страница 8: ...vate in menu 9 1 3 Fighter 11XX Activate in menu 9 2 15 Fighter 12XX Fighter 13XX Activate in menu 9 1 3 11 12 14 13 Start the web browser and enter the RCUs IP address in the address field and press...

Страница 9: ...DHCP is selected in the RCU If the DHCP is not to be used close the DHCP with Netbiter Continue with network settings for the RCU No page is shown when entering the RCU IP address in the web browser S...

Страница 10: ...ute the communication cable 105 down to the area at the bottom of the heat pump Use the supplied connector to connect the commu nication cable from the RCU The CPU card in FIGHTER 360P must have versi...

Страница 11: ...modular cable between the CPU card 34 and the communication card 3 If one or more slaves are connected the remaining modular cable to the com munication card 3 must be connected to the socket oppo sit...

Страница 12: ...commended For connection direct to a compu ter with Internet connection two network cards are requi red in the computer and it must run continuously in order to provide the RCU access to the Internet...

Страница 13: ...n be done in a mobile telephone or by the ser vice provider For a telephonic data connection to the RCU the SIM card needs to have a special telephone number for computer communication Refer to the se...

Страница 14: ...red During startup Not lit No contact with network Steady green 10 Mbit s link Steady orange 100 Mbit s link Not lit Waiting Flashing green TX serial channel serial package receive Flashing red RX ser...

Страница 15: ...rd disk space Windows 95 98 ME NT 2000 XP Network card Ethernet If a different operating system than Windows is used the configuration software can not be used Then connect to the RCU s preset IP addr...

Страница 16: ...he new set tings can be entered To obtain the necessary information concerning your net work settings please contact your network administrator IP Address IP address for the RCU Subnet mask Network ma...

Страница 17: ...irst time enter admin into both entry fields Another log in dia log can be shown depending on the Java version installed The password will be changed later and new users can be added refer to the Web...

Страница 18: ...also a version on the supplied CD The side menu provides navigation in the RCU s internal web pages The side menu has differences depending on which product is used together with the RCU Overview diag...

Страница 19: ...og file change at restart of the RCU or when the log in settings are changed Log In Settings Log are entered the desired paramet ers logging interval and type of log in The selected parameters and log...

Страница 20: ...service personnel E mail Here the settings for handling E mail can be made This is necessary for enabling the RCU to send alarms via E mail to selected users E mail Activates E mail function SMTP serv...

Страница 21: ...formation can be edited by clicking on the names User ID This ID is used when logging on to the RCU via a browser Name User s name E mail The user s E mail address to which alarms are to be sent Mobil...

Страница 22: ...eturn temperature Menu 2 6 C Temperature compressor sensor Menu 1 1 D Temperature hot water sensor Menu 1 0 E Evaporation temperature Menu 5 0 F Extract air temperature Menu 5 1 G Exhaust air temperat...

Страница 23: ...After a few seconds the change is confirmed by FIGHTER 360P and the relevant value is updated The change in value presumes that the user has logged in with writing or administration authority Operati...

Страница 24: ...pro gram for further processing Alarm status This form shows the common alarms that the heat pump has indicated External alarm inputs DI1 and DI2 are not concerned with the heat pump functions but ar...

Страница 25: ...o Electric Boiler XHW 0 3 6 12 24 Extra hot water function Vent 0 1 N 2 Fan speed Off Speed 1 Normal Speed 2 DI 1 2 12 RCU digital inputs STATUS2 Vent nn n Extract air temperature Exh nn n Exhaust air...

Страница 26: ...n C Operational information Here the status is shown of the functions that are ac tivated in the heat pump Overview diagram This is the first page to be displayed after logging in It shows an overview...

Страница 27: ...1 0 Note that the selected RCU offset heating curve is added to the heat pump s internal offset heating curve To change a value click on arrow down and select a va lue from the scrolling list confirm...

Страница 28: ...hat the user has logged in with writing or administration authority Operating data external units In this form the external unit parameters can be changed by clicking on arrow down and selecting a val...

Страница 29: ...terface FIGHTER 1250 A Communication indications Green lamp indicates functioning communications Red lamp indicates communication error B Operating indications Lit lamp indicates an active function C...

Страница 30: ...ffset heating curve is added to the heat pump s internal offset heating curve To change a value click on arrow down and select a va lue from the scrolling list confirm with Set After a few seconds the...

Страница 31: ...In this form the heat regulation parameters can be chan ged by clicking on arrow down and selecting a value from the scrolling list confirming thereafter with Set The change in value presumes that the...

Страница 32: ...his form the external unit parameters can be changed by clicking on arrow down and selecting a value from the scrolling list confirming thereafter with Set The change in value presumes that the user h...

Страница 33: ...ata extended Log Here the log files that are in the RCU can be fetched The parameter log contains selected logged values see the Web interface Settings Log section The alarm log contains all the alarm...

Страница 34: ...Brine out temperature HW On Off Hot water production activated Mode W SA S A Add heat ONLY FIGHTER 11XX 12XX Operating mode Winter Spring Autumn Summer Auto Additional Only S A Add heat ONLY FIGHTER...

Страница 35: ...red marker indicates which unit is being shown Slave is only shown when several heat pumps are connected to the Master B Operating indications Shows operating conditions for installed units Green back...

Страница 36: ...that the selected RCU offset heating curve is added to the heat pump s internal offset heating curve To change a value click on arrow down and select a va lue from the scrolling list confirm with Set...

Страница 37: ...e changed by clicking on arrow down and selecting a value from the scrolling list confirming thereafter with Set The change in value presumes that the user has logged in with writing or administration...

Страница 38: ...witch between different heat pumps in the system by using the scroll list at the top left The change in value presumes that the user has logged in with writing or administration authority Log Here the...

Страница 39: ...ected C F nn n Calculated flow DM nn n Current degree minutes Mode W SA S A Add heat Operating mode Winter Spring Autumn Summer Auto Additional Only XHW 0 3 6 12 24 Extra hot water function A heat On...

Страница 40: ...ications module with GSM modem 3 Antenna 4 Communication port to FIGHTER 5 Network connections 6 Eject button and holder for SIM card 7 Connection of external contact function 8 Label with MAC ID RCU...

Страница 41: ...emperature range 0 60 C CE certification In accordance with EN 50 081 2 1993 and EN 61 000 6 2 1999 Miscellaneous Miscellaneous Enclosed kit L E K LEK LEK LEK LEK LEK Network cable cross over for conn...

Страница 42: ...sible to call in to an RCU if you have a modem connected to a computer and have configured the RCU to accept this Via this connection it is then possible to look at the web pages and download log file...

Страница 43: ......

Страница 44: ...LLEMSTAD NB Tel 0168 477722 Fax 0168 476998 E mail info nibenl nl www nibenl nl V lund Varmeteknik Filial af NIBE AB Brog rdsvej 7 6920 Videb k Tel 97 17 20 33 Fax 97 17 29 33 E mail info volundvt dk...

Отзывы: