Advance Setting
Move your mouse to the circle on top of ZB11C.
Then right click your mouse should display menu and select
Advance
.
IR disabling duration
User is able to configure motion sensing disabling period following the previous motion
detection. Default time is 120 seconds. Refer to figure bellow.
-Click
Set IR Disabled Time
button.
Before you click on it make sure you wakeup the
ZB11C device so that the setting can be written into the device. This is also true for the
following two settings.
Assigning a CIE device
User is able to reassign the zone device to another CIE device in the network.
-Select a CIE device from the dropdown menu then click on
Set IAS_CIE_ADDRESS
button. When successfully registered to the new CIE, the LED on ZB11C will flash 6 times.
Zone Device Alive Indication
ZB11C periodically sends heartbeats to the network to notify the network that it is still
working and alive. This is particular important feature as part of security system. Most
users would want to make sure that security device are up and working. After 3 missing
heartbeats, ZiG-BUTLER would notify the user. The user may diagnose of its power or
device tampering.
-enter the time interval. In the example, 1 hour means the device only sent one
heartbeat per hour.