Having done that, now configure the reporting time interval
Now move your mouse to the circle on top of ZB11C icon. Then right click your mouse
should display menu and select
Property.
Go to
Report Config
tab, similar to the figure bellow.
Figure: temperature reporting interval configuration
Minimum reporting time interval (Min)
–this is the minimum temperature sampling time
interval, in seconds, between issuing temperature reports. If this value is set to 0, then
there is no minimum limit.
Maximum reporting time interval (Max)
–this is the fixed time sampling interval, in
seconds, between issuing temperature reports. If this value is set to 0, then the device
shall not report the temperature.
Reportable change
– this is the minimum temperature change that will result in a report
being issued. If the change in temperature
is greater than
the set
Reportable Change
temperature value, the device issues report the detected temperature at the
Min
-minimum reporting time. If the change
is less than
, the reportable change will not report
until the time reaches to the
Max
-maximum reporting time.
Explain: The reportable change (in unit
o
C) is the actual difference in temperature
between the current and the previously reported. It tells the system that if the
temperature difference is said to be
greater than
the previously reported temperature