Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 10
"Minimum Cool 1 Heat 1 Percent"
Default:
Range:
Increment:
0 %
0 to 100%
5 %
This option appears if you have selected
CH1
at Step 17, "AO2 Ramp" or at Step 22,
“AO3 Ramp”. Set the percentage at
which the controller sets the CH1 output during heating, provided another output has also been set to heating.
Fan Settings
"Fan Spd Signal"
Default:
Range:
3
1, 2, 3
This option does not appear if you have selected
FAN
at Step 17, "AO2 Ramp". Select the desired number of fan speed
contacts. The fan
symbol is also displayed.
"Fan Speed Option"
Default:
Range:
Std (Standard)
AdV (Advanced), Std (Standard)
Select between the Standard (Neptronic) and Advanced (OE1) fan speed specifications. The fan
symbol is also displayed.
"Enable Fan Contrl Mode"
Default:
Range:
No (Disable)
yES (Enable), No (Disable)
This option appears only if you have selected
Adv
at Step 29, "Fan Speed Option". Select to enable or disable the fan control
mode option. If you select
No
, the Fan Speed Selection Mode option is not available in Control Mode. The fan
symbol is
also displayed.
"Hide Fan Display Info"
Default:
Range:
No (Disable)
yES (Enable), No (Disable)
Select to enable or disable the fan display information. If you select
Yes
, the Fan demand (fan icon) does not appear on the
display and the Fan Speed Selection Mode is disabled. The fan
symbol is also displayed.
"Fan Auto Mode"
Default:
Range:
yES (Enable)
yES (Enable), No (Disable)
If set to
yES
, the user can set the fan speed to "Automatic" via the Fan Speed Selection Mode (see page 31). If set to
No
, the
"
Automatic
" speed does not appear in the Fan Speed Selection Mode. The fan
symbol is also displayed.
If you select yES, Step 33 "Fan Auto Timeout Seconds" will be available.
If you select No, Step 33 "Fan Auto Timeout Seconds" will not be available.
"Fan Auto Timeout Seconds"
Default:
Range:
Increment:
120 seconds
0 to 255 seconds
1 second
This option appears only if you have selected
yES
at Step 32, "Fan Auto Mode". Select the desired value for the automatic
shutoff delay when there is no demand. The fan
symbol is also displayed.
"Damping Factor Time In Seconds"
Default:
Range:
Increment:
0 second
0 to 255 seconds
1 second
Select the desired damping factor value for the fan. The fan