Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 16
"Cool 1 Prop Band"
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5ºC to 5.0ºC
[1ºF to 9ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the cooling ramp 1. The cooling
symbol is also displayed.
"Cool 1 Dead Band"
Default:
Range:
Increment:
0.3ºC
[0.6ºF]
0ºC to 5.0ºC
[0ºF to 9ºF]
0.1ºC
[0.2ºF]
Select the desired dead band value of the cooling ramp 1. The cooling
symbol is also displayed.
"Cool 2 Prop Band"
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5ºC to 5.0ºC
[1ºF to 9ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the cooling ramp 2. The cooling
symbol is also displayed.
"Cool 2 Dead Band"
Default:
Range:
Increment:
0.3ºC
[0.6ºF]
0.0ºC to 5.0ºC
[0ºF to 9ºF]
0.1ºC
[0.2ºF]
Select the desired dead band value of the cooling ramp 2. The cooling
symbol is also displayed.
"Cooling Anti Cycle Minutes"
Default:
Range:
Increment:
2 minutes
0 to 15 minutes
1 minute
To protect the compressor, set the delay in minutes before activating or reactivating the cooling output. The cooling
symbol
is also displayed.
"Heating Intgral Time In Seconds"
Default:
Range:
Increment:
0 seconds
0 to 250 seconds
5 seconds
Set the desired value for heating integration factor compensation. The heating symbol is also displayed.
"Cooling Intgral Time In Seconds"
Default:
Range:
Increment:
0 seconds
0 to 250 seconds
5 seconds
Set the desired value for cooling integration factor compensation. The cooling
symbol is also displayed.
"Cl Ht Switch Timer Minutes"
Default:
Range:
Increment:
0 minutes
0 to 120 minutes
1 minute
Time required in minutes before a changeover can take place. The cooling
and heating symbols are also displayed.
Universal Input 1 (UI1)
"UI1 Signal Type"
UI1
Default:
Range:
OFF
OFF, t10.0, SENs, noCL, noHt, OAS, t10V, CO2, OCC,
nSb, oVrd, win, door, dFt, FLS, oVht, SEL, FrFb, HU, P10V, t01
2,
dt1t, dt1u, dt0t, dt0u
Select the input signal type for UI1(Universal Input 1).
•
OFF. If selected, the controller does not use the input.
•
t10.0. If selected, the controller uses
a 10kΩ type III external temperature sensor. If you select t10.0, Step 90, "Extern
Temp Sensor Offset" will be available.