Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 15
“BO7 Dirrev”
BO7
Default:
Range:
dir (Direct)
dir (Direct), rEV (Reverse)
This option does not appear if the signal ramp for BO7 is set to
OFF
(Step 60,
“BO7 Ramp”). Set the direction of the binary
signal to either Direct or Reverse.
“BO7 Contact Delay Minutes”
BO7
Default:
Range:
Increment:
0 minute
0 to 15 minutes
1 minute
This option does not appear if the signal ramp for BO7 is set to
OFF
(Step 60,
“BO7 Ramp”). Select the closing delay for BO7
output.
“BO7 Signal Type”
BO7
Default:
Range:
OnO
F
(On/Off)
tPm (Pulsing), OnO
F
(On/Off), FLot (Floating)
This option does not appear if the signal ramp for BO7 is set to
OFF
(Step 60,
“BO7 Ramp”). Select the signal type for BO7 to
either Pulsing, On/Off or Floating.
Proportional and Deadband Settings
"CH Over Prop Band"
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5ºC to 5.0ºC
[1ºF to 9ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the changeover ramp. The cooling
and heating symbols are also displayed.
"CH Over Dead Band"
Default:
Range:
Increment:
0.3ºC
[0.6ºF]
0.0ºC to 5.0ºC
[0ºF to 9ºF]
0.1ºC
[0.2ºF]
Select the desired dead band value of the changeover ramp. The cooling
and heating symbols are also displayed.
"Heat 1 Prop Band"
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5ºC to 5.0ºC
[1ºF to 9ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the heating ramp 1. The heating symbol is also displayed.
"Heat 1 Dead Band"
Default:
Range:
Increment:
0.3ºC
[0.6ºF]
0.0ºC to 5.0ºC
[0ºF to 9ºF]
0.1ºC
[0.2ºF]
Select the desired dead band value of the heating ramp 1. The heating symbol is also displayed.
"Heat 2 Prop Band"
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5ºC to 5.0ºC
[1ºF to 9ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the heating ramp 2. The heating symbol is also displayed.
"Heat 2 Dead Band"
Default:
Range:
Increment:
0.3ºC
[0.6ºF]
0.0ºC to 5.0ºC
[0ºF to 9ºF]
0.1ºC
[0.2ºF]
Select the desired dead band value of the heating ramp 2. The heating symbol is also displayed.