Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 22
"Window Fan Mode"
Default:
Range:
AUto (Automatic)
AUto (Automatic), LO (Low), mEd (Medium), HI (High)
This option appears only if you have selected
win
at Step 80, "UI1 Signal Type" or Step 84, "UI2 Signal Type". Select the fan
speed mode when the window is open. The fan
and alarm
symbols are also displayed.
"Door Open Mode"
Default:
Range:
StP (Setpoint/override enabled)
StP (Setpoint/override enabled), OFF
This option appears only if you have selected
door
at Step 80, "UI1 Signal Type" or Step 84, "UI2 Signal Type".
•
StP. If selected, the controller uses the NSB/No Occupancy setpoints when the door is open.
•
OFF. If selected, the controller is forced into OFF mode when the door is open.
"Door Fan Mode"
Default:
Range:
AUto (Automatic)
AUto (Automatic), LO (Low), mEd (Medium), HI (High)
This option appears only if you have selected
door
at Step 80, "UI1 Signal Type" or Step 84, "UI2 Signal Type". Select the fan
speed when the door is open. The fan
and alarm
symbols are also displayed.
Night Set Back (NSB)
“NSB
Overide
Delay Minutes”
Default:
Range:
Increment:
120 minutes
0 to 180 minutes
15 minutes
This option appears only if you have selected
nSb
at Step 80, "UI1 Signal Type" or Step 84, "UI2 Signal Type". When in Night
Set Back (NSB) Mode, the user can override Night Set Back (NSB) (see page 31) for the duration of this delay. To disable
night set back override, set the delay to 0. The moon symbol is displayed to indicate Night Set Back (NSB) Mode.
"NSB Fan Mode"
Default:
Range:
AUto (Automatic)
AUto (Automatic), LO (Low), mEd (Medium), HI (High)
This option appears only if you have selected
nSb
at Step 80, "UI1 Signal Type" or Step 84, "UI2 Signal Type". Select the fan
speed mode for night set back. The fan
symbol is also displayed.
"Nsb Mode"
Default:
Range:
StP (Setpoint/override enabled)
StP (Setpoint/override enabled), OFF
This option appears only if you have selected
nSb
at Step 80, "UI1 Signal Type" or Step 84, "UI2 Signal Type".
•
StP. If selected, the controller uses the NSB setpoints when in Night Set Back (NSB) Mode. (see page 31).
•
OFF. If selected, the controller is forced into OFF mode when in Night Set Back (NSB) Mode. (see page 31).
"NSB Heating Setpnt"
Default:
Range:
Increment:
16ºC
[61ºF]
10ºC to 40ºC
[50ºF to 104ºF]
0.5ºC
[1ºF]
This option appears only if you have selected
nSb
at Step 80, "UI1 Signal Type" or Step 84, "UI2 Signal Type". Set the heating
setpoint that will be used when the system is in Night Set Back (NSB) Mode (see page 31). The heating setpoint value is
restricted by the cooling setpoint value at Step 114, "NSB Cooling Setpnt". The moon and heating symbols are also
displayed.
"NSB Cooling Setpnt"
Default:
Range:
Increment:
28ºC
[82ºF]
10ºC to 40ºC [50ºF to 104ºF]
0.5ºC
[1ºF]
This option appears only if you have selected
nSb
at Step 80, "UI1 Signal Type" or Step 84, "UI2 Signal Type". Set the cooling
setpoint that will be used when the system is in Night Set Back (NSB) Mode (see page 31). The cooling setpoint value is
restricted by the heating setpoint value at Step 113, "NSB Heating Setpnt". The moon and cooling
symbols are also
displayed.