Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 26
"Humidty Prop Ramp"
Default:
Range:
Increment:
5% RH
3% RH to 10% RH
0.5% RH
This option appears only if you have selected
AuTo
,
Hu
or
deHU
at Step 123, "Humidty Control Mode". Set the desired
proportional ramp value for the humidity control. This value applies to both humidification and dehumidification.
"Humidty Dead Band"
Default:
Range:
Increment:
1% RH
0% RH to 5% RH
0.5% RH
This option appears only if you have selected
AuTo
,
Hu
or
deHU
at Step 123, "Humidty Control Mode". Set the desired dead
band value for the humidity control. This value applies to both humidification and dehumidification.
Anti Freeze
"Enable Anti Freeze Protect"
Default:
Range:
No (Disable)
No (Disable), Yes (Enable)
If this option is enabled, heating starts automatically when the temperature drops to 4°C [39°F], even if the controller is in
Cooling or OFF mode. Once the temperature reaches 5°C [41°F], the heating stops.
Delta Temperature
“Enable Delta Temp Mode”
Default:
Range:
OFF
On, OFF
Select whether to enable or disable the
ΔT control based on the inlet and outlet temperature of the water inside the fan coil
unit.
Backlight Adjustment
“User Back Light Adjust”
Default:
Range:
Increment:
50
0 to 100
5
Select the backlight level in the user mode (controller is in operation). Use the
and
buttons to increase or decrease the
backlight level.
“Occ Back Light Adjust”
Default:
Range:
Increment:
50
0 to 100
5
Select the backlight level in the occupied mode (controller is idle and occupancy state is active). Use the
and
buttons to
increase or decrease the backlight level.
“No Occ Back Light Adjust”
Default:
Range:
Increment:
50
0 to 100
5
Select the backlight level in the not occupied mode (controller is idle and occupancy state is inactive). Use the
and
buttons to increase or decrease the backlight level.