Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 18
oVrd
win
door
dFt
FLS
oVht
SEL
FrFb
HU
PI0u
t01
2
dt1t
dt1u
dt0t
dt0u
"UI1 Minimum Voltage"
UI1
Default:
Range:
2.0
0.0, 2.0
This option appears only if you have selected either
P10V
or
t10V
at Step 80, "UI1 Signal Type". Select the minimum voltage
for UI1.
"UI1 Contact"
UI1
Default:
Range:
NO (Normally Open)
NO (Normally Open), NC (Normally Close)
This option appears only if you have selected any one of the options:
OCC
,
nSb
,
oVrd
,
win
,
door
,
dFt
,
FLS
,
oVht
,
SEL
at
Step 80, "UI1 Signal Type". Select the desired contact option.
"UI1 Delay Seconds"
UI1
Default:
Range:
Increment:
120 seconds
0 to 3600 seconds
10 seconds
This option appears if you have selected any one of the options:
oVrd
,
win
,
door
,
dFt
,
FLS
,
oVht
,
SEL
at Step 80, "UI1 Signal
Type". Set the delay in seconds before the state of input for UI1 is changed.
Universal Input 2 (UI2)
"UI2 Signal Type"
UI2
Default:
Range:
OFF
OFF, t10.0, SENs, noCL, noHt, OAS, t10V, CO2, OCC,
nSb, oVrd, win, door, dFt, FLS, oVht, SEL, HU, P10V, t012
Select the input signal type for UI2 (Universal Input 2). Same options as Step 80, "UI1 Signal Type".
•
The UI1 input signal has priority over UI2. If you select the same input signal type as UI1, UI2 will not be functional.
If you select one of the following options:
OFF
,
noCL
,
noHt
,
OAS
or
HU
, Steps 85 to 93 will not be available.
If you select
t10.0
, Steps 85 to 89 will not be available.
If you select
t10V
, Steps 86 and 87 will not be available.
If you select
SENs
, Steps 85 to 90 will not be available.
If you select
CO2
, Steps 85 to 104 will not be available.
If you select
P10V
or
t10V
, Step 85, "UI2 Minimum Voltage" will be available.
If you select
P10V,
Step 95, "Pressur Maximum Range" will be available.