Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 25
"Humidty User Setpnt Maximum"
Default:
Range:
Increment:
65% RH
10% RH to 90% RH
0.5% RH
This option appears only if you have selected
AuTo
,
Hu
or
deHU
at Step 123, "Humidty Control Mode". In Operation mode,
you cannot increase the setpoint to more than the value set as the maximum humidity setpoint. The maximum value is
restricted by the minimum value set at Step 126, "Humidty User Setpnt Minimum". In other words, the value that is set as the
maximum cannot be less than the minimum value.
"Humidity User Setpnt Locked"
Default:
Range:
No (Unlocked)
No (Unlocked), Yes (Locked)
This option appears only if you have selected
AuTo
,
Hu
or
deHU
at Step 123, "Humidty Control Mode". If set to
No
, the user
setpoint option is not locked and the user can adjust the desired humidity setpoint. If set to
Yes
, the user setpoint option is
locked and the user cannot set the desired humidity setpoint. A lock symbol appears to indicate that the setpoint is locked.
"Humidty User Setpnt"
Default:
Range:
Increment:
40% RH
10% RH to 90% RH
0.5% RH
This option appears only if you have selected
AuTo
,
Hu
or
deHU
at Step 123, "Humidty Control Mode". Set the desired
humidity setpoint. If the setpoint option was locked at Step 128, "Humidity User Setpnt Locked", a lock symbol is displayed.
The setpoint value is restricted by the minimum at Step 126, "Humidty User Setpnt Minimum" and maximum at Step 127,
"Humidty User Setpnt Maximum" values.
"NSB Humidif Setpnt"
Default:
Range:
Increment:
30% RH
10% RH to 65% RH
0.5% RH
This option appears only if you have selected
AuTo
,
Hu
or
deHU
at Step 123, "Humidty Control Mode",
and also
nSb
at
Step
80, "UI1 Signal Type" or Step 84, "UI2 Signal Type". Adjust the humidify setpoint during Night Set Back (NSB) Mode. The
humidify setpoint is restricted by the dehumidify value at Step 131, "NSB Dehumi- Setpnt". The moon and humidify
symbols are also displayed.
"NSB Dehumi- Setpnt"
Default:
Range:
Increment:
45% RH
10% RH to 65% RH
0.5% RH
This option appears only if you have selected
AuTo
,
Hu
or
deHU
at Step 123, "Humidty Control Mode",
and also
nSb
at
Step
80, "UI1 Signal Type" or Step 84, "UI2 Signal Type".
Adjust the dehumidify setpoint during Night Set Back (NSB) Mode. The
dehumidify setpoint is restricted by the humidify setpoint at Step 130, "NSB Humidif Setpnt". The moon and dehumidify
symbols are also displayed.
"No OCC Humidif Setpnt"
Default:
Range:
Increment:
30% RH
10% RH to 65% RH
0.5% RH
This option appears only if you have selected
AuTo
,
Hu
or
deHU
at Step 123, "Humidty Control Mode",
and also
OCC
at
Step
80, "UI1 Signal Type" or Step 84, "UI2 Signal Type".
Adjust the humidify setpoint during No Occupancy Mode. The humidify
setpoint is restricted by the dehumidify value at Step 133, "No OCC Dehumi - Setpnt". The moon and humidify
symbols
are also displayed.
"No OCC Dehumi - Setpnt"
Default:
Range:
Increment:
45% RH
10% RH to 65% RH
0.5% RH
This option appears only if you have selected
AuTo
,
Hu
or
deHU
at Step 123, "Humidty Control Mode", and also
OCC
at
Step
80, "UI1 Signal Type" or Step 84, "UI2 Signal Type". Adjust the dehumidify setpoint during No Occupancy Mode. The
dehumidify setpoint is restricted by the humidify setpoint at Step 132, "No OCC Humidif Setpnt". The moon and dehumidify
symbols are also displayed.