Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 14
•
VFdP (VFD Pressure Loop). If selected, the controller will modulate the static pressure based on the reading and the
pressure setpoint.
"BO6 Close Percent"
Default:
Range:
Increment:
20% of the demand
15 to 80%
1%
This option does not appear if the signal ramp for BO6 is set to
OFF
(Step 54, "BO6 Ramp"). Select the percentage at which
you want BO6 to close (at % of demand of the ramp selected at Step 54, "BO6 Ramp").
"BO6 Open Percent"
Default:
Range:
Increment:
0% of the demand
0 to (BO6 Close)-4%
1%
This option does not appear if the signal ramp for BO6 is set to
OFF
(Step 54, "BO6 Ramp"). Select the percentage at which
you want BO6 to open (at % of demand of the ramp selected at Step 54, "BO6 Ramp").
"BO6 Dirrev"
Default:
Range:
dir (Direct)
dir (Direct), rEV (Reverse)
This option does not appear if the signal ramp for BO6 is set to
OFF
(Step 54, "BO6 Ramp"). Set the direction of the binary
signal to either Direct or Reverse.
"BO6 Contact Delay Minutes"
Default:
Range:
Increment:
0 minute
0 to 15 minutes
1 minute
This option does not appear if the signal ramp for BO6 is set to
OFF
(Step 54, "BO6 Ramp"). Select the closing delay for BO6
output.
“BO6 Signal Type”
Default:
Range:
OnO
F
(On/Off)
tPm (Pulsing), OnO
F
(On/Off), FLot (Floating)
This option does not appear if the signal ramp for BO6 is set to
OFF
(Step 54, "BO6 Ramp"). Select the signal type for BO6 to
either Pulsing or On/Off. If the BO5 signal type is set to Floating, then BO6 signal type will also be set to Floating.
Binary Output 7 (BO7)
“BO7 Ramp”
BO7
Default:
Range:
OFF
Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr
Select the desired ramp from the available options. Same as BO3 options.
If you select
OFF
, Steps 61 to 65 will not be available.
“BO7 Close Percent”
BO7
Default:
Range:
Increment:
20% of the demand
15 to 80%
1%
This option does not appear if the signal ramp for BO7 is set to
OFF
(Step 60,
“BO7 Ramp”). Select the percentage at which
you want BO7 to close (at % of demand of the ramp selected at Step 60,
“BO7 Open Percent”
BO7
Default:
Range:
Increment:
0% of the demand
0 to (BO6 Close)-4%
1%
This option does not appear if the signal ramp for BO6 is set to
OFF
(Step 60,
“BO7 Ramp”). Select the percentage at which
you want BO7 to open (at % of demand of the ramp selected at Step 60,