80 Troubleshooting
Testing method
Fault
Possible causes
Testing method
Heat exchanger overheat
Damaged or obstructed
heat exchanger
1. High exhaust gas temperatures can cause damage to or obstruct the heat
exchanger.
2. Flush the heat exchanger to remove scale deposits.
3. Replace the heat exchanger if it is damaged or cannot be unclogged.
Defective part
Defective overheat
controller
Faulty terminals on the exhaust gas overheat controller (110°C max)
●
Check the overheat controller’s wiring connections.
●
If the resistance is incorrect, replace the temperature sensor.
●
Check the output temperature displayed on the PCB.
Test if the hot water temperature sensor is open (error result: MΩ open)
Other faults
PCB fault
If the error condition continues after checking these items, replace the PCB.
5.2.7 Error 031
Is the burner overheat
prevention disconnected?
Check the PCB.
Replace the burner overheat
prevention.
Yes
No
Содержание NCB-700-2S+/42K
Страница 3: ......
Страница 4: ...Revisions 3 Version Description of changes Date 1 00 First issue July 11 2022 Revisions...
Страница 119: ...Memo...
Страница 120: ...Memo...
Страница 121: ...Memo...