Troubleshooting 63
Error Code Sub Code
Function
Diagnosis/Actions
E109
0
Fan motor activity error
1. Check and clean the air intake filter.
2. Check and clean the fan motor.
3. Test the voltage from the PCB to ensure that it is correct. Replace
fan if PCB voltage is normal.
E110
0
Exhaust blockage (Condensate
blockage)
1. Check the exhaust pipe for obstructions.
2. Check and clean the intake air filter.
3. If possible, remove the exhaust pipe to ensure that the flue is clear.
E127
0
APS error
1. Check the APS.
2. Check APS wiring connections
E205
1
Heating supply thermistor open
error
1. Check the thermistor.
2. Check pump wiring connections.
2
Heating supply thermistor short
error
E218
1
Heating return thermistor open
error
1. Check the thermistor.
2
Heating return thermistor short
error
E291
3
Supply / Return inversion limit
Check the direct water connection.
E302
0
Low water pressure
1. Check the feeder valve.
2. Check the incoming water pressure and activity at the PRV.
E352
0
High water pressure
1. Check the feeder valve.
2. Check the incoming water pressure and activity at the PRV.
E353
1
Water pressure sensor open error
Check the water pressure sensor.
2
Water pressure sensor short error
E407
1
Hot water outlet thermistor open
error
1. Check the thermistor.
2. Replace the thermistor.
2
Hot water outlet thermistor short
error
E421
1
Cold water inlet thermistor open
error
1. Check the thermistor.
2. Replace the thermistor.
2
Cold water inlet thermistor short
error
E434
1
Abnormal operation: Flow control
value
E441
1
DHW Outlet 2 thermistor open or
short circuit
E445
1
Abnormal operation: Mixing valve
E480
1
DHW tank thermistor open circuit
2
DHW tank thermistor short circuit
E515
Abnormal operation: Relay
feedback (PCB)