82 Troubleshooting
5.2.10 Error 060
Error Conditions and Checklist
Error
Description
E060
Dual venturi error
Dual venturi wiring is disconnected or the dual venturi malfunctions.
The boiler switches to Lock-out mode, performs a continuous post-purge continuously,
and starts the circulation pump.
Check items
1. Check that the dual venturi is operating correctly. Run in dual venturi test mode.
2. Check that the wiring harness is connected correctly and the cables are not damaged.
Is the dual venturi closed?
Does the dual venturi
repeatedly open
and close?
Replace the controller
Is the dual venturi OFF?
Reset the
boiler
Replace the
dual venturi
Yes
Yes
No
No
Is the dual venturi
open?
Is the dual venturi wiring
connection correct?
Does the dual venturi
repeatedly open
and close?
Replace the controller
Is the dual venturi ON?
Reset the
boiler
Check the
dual venturi
wiring
Replace the
dual venturi
Yes
No
Yes
No
Yes
No
Dual venturi OFF
Dual venturi ON