26 System Details
d. After Gas Setup Wizard is done, operate at 1-stage MIN
mode.
Note
For operation mode selection, refer to“4.4.8.5
Setting the Special Operation Modes” on
e. Fully open several hot water fixtures and set the boiler
to operate at 2-stage D. MAX mode (refer to “4.4.8.5
Setting the Special Operation Modes” on page 40).
Measure the CO₂ value at high fire.
If the CO₂ values do not match Table 2 at high fire,
do not adjust the gas valve. Check for the proper Gas
Orifice.
DANGER
Improper gas valve settings can cause severe personal injury
or substantial property damage.
c. Fully open several hot water fixtures and set the boiler
to operate, and proceed Gas Setup Wizard.
Note
For proceeding Gas Setup Wizard for gas type
selection, refer to “4.4.4 Set-Up Wizard” on
Measure the CO₂ value at low fire.
If the CO₂ value is not within 0.5% of the value listed in
Table 2, the gas valve set screw will need to be adjusted.
If adjustment is necessary, locate the set screw as shown
in Figure 8. Using a
5
/
32
in or 4 mm Allen wrench, turn
the set screw no more than
1
/
4
turn clockwise to raise or
counterclockwise to lower the CO₂ value.
Figure 8. Set Screw Location
Note
The set screw is located behind the screw-on
cover. This must be removed first.
Model
Gas type
G20
G31
[20 mbar]
[37 mbar]
Output
Consumption
Gas flow
Gas flow
Load
Kcal/h
kW
kW
m
3
/h
m
3
/h
NCB700-2S+/42K
Max.
29,240
34
35
3.33
1.32
Min.
2,924
3.4
3.5
0.33
0.13
NCB700-3S/54K
Max.
29,240
34
35
3.33
1.32
Min.
2,924
3.4
3.5
0.33
0.13