Troubleshooting 81
5.2.8 Error 046
Is the heat exchanger’s
thermistor operating
correctly?
Is the resistance
within the normal range?
Replace heat exchanger
thermistor.
Check connections
Step 1: Flush, clean Filter
Step 2: Restart
Step 3: Replace PCB
Yes
Yes
No
No
5.2.9 Error 047
Error Conditions and Checklist
Is the exhaust thermistor
operating correctly?
Check connection
Replace exhaust thermistor
No
Yes